Amphenol Telaire Ventostat T8100 NS Series Istruzioni per l'utente - Pagina 3

Sfoglia online o scarica il pdf Istruzioni per l'utente per Accessories Amphenol Telaire Ventostat T8100 NS Series. Amphenol Telaire Ventostat T8100 NS Series 4. Co2 sensor

Amphenol Telaire Ventostat T8100 NS Series Istruzioni per l'utente
Ventostat Specifications
Sensing Method
Non-dispersive infrared (NDIR) absorption
Gold-plated optics
Patented ABC Logic self calibration algorithm
CO
Measurement Range
2
T8100
0 to 2000 ppm (0 ppm = 0 V, 4 mA; 2000 ppm = 10/5V, 20 mA)
CO
Accuracy
2
±30 ppm or 3% of reading, whichever is higher*
Power Supply Requirements
18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected
Power Consumption
Typical 0.7 W at nominal voltage of 24V AC RMS
Temperature Dependence
0.2% FS per °C (±0.11% per °F)
Stability
<2% of FS over life of sensor (15 years)
Pressure Dependence
0.135% of reading per mm Hg
Certifications
CE and RoHS compliant
Signal Update
Every 5 seconds
CO
Warm-up Time
2
< 2 minutes (operational)
10 minutes (maximum accuracy)
Operating Conditions
32°F to 122°F (0°C to 50°C)
0 to 95% RH, non-condensing
*CO
accuracy statement excludes standard gas used for calibration that
2
has an accuracy of 2%. In addition, there is a potential digital to analog
error of up to 1%.
Telaire Ventostat™ T8100 NS and NSP Series
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Flammability Classification
UL94 5VA
Thermistor Type
NTC 10 Kthermistor
Thermistor Accuracy
±1°C (15° to 35°C)
Night Setback Override Button (NS and NSP)
Shorts the thermistor output when depressed
Slide Potentiometer (NSP Only)
Left (stop) 0k Ohms (±5k )
Center 50k Ohms (±7.5k )
Right (stop) 100k Ohms (±15 )
ABC Logic™ Self Calibration System
ABC Logic™ (Automatic Background Calibration) self calibration
allows the sensor to continually recalibrate itself when the indoor
concentrations drop to outside levels while the building is unoccupied.
Generally a building must be regularly unoccupied for 4 hours or more
for this self-calibration system to operate properly. Under these
conditions, ABC Logic™ should maintain sensor calibration over the
lifetime of the sensor. The ABC Logic™ should be turned OFF where a
building is continuously occupied 24 hours per day, or where there could
be significant sources of non-occupant related CO
breweries and other industrial and food processing applications.
Output
Analog
0 to 5 V, (100  output impedance)
0 to 10 V (100  output impedance) and
maximum 500 ) available simultaneously for CO
4 to 20mA (R
L
output
Digital to analog error ±1%
such as greenhouses,
2
2
Page 3