3.1 Location and Suspension
All Models:
•
Must be installed indoors.
•
Must be installed in a level position.
•
Fan must be suspended from above (See Page 6,
Figure 3). Drop rods must be a minimum of 10mm
diameter mild steel. Four suspension points (M10
nuts) are located on top of fan. Mounting hardware
must be sufficient to support fan weight as listed in
the dimension data on Page 5, Section 2.3.
•
Must be installed in a manner which allows access
to all serviceable components.
3.2 Minimum Required Installation Clearances
Clearances around fan must be as indicated on Page
5, Section 2.3 to ensure access for servicing and
correct operation.
FIGURE 3: Suspension Methods
6
Section 3
Combat Limited HVE Energy Saving Fans, Installation, Operation and Service Manual
Critical Considerations