AirStage ABHA36GATH Manuale di installazione - Pagina 15
Sfoglia online o scarica il pdf Manuale di installazione per Condizionatore d'aria AirStage ABHA36GATH. AirStage ABHA36GATH 17. Indoor unit (ceiling type)
Function
Function
Setting number
number
00
Default
Heat air
01
Adjust (1)
tem-
31
perature
02
Adjust (2)
trigger
03
Adjust (3)
00
Enable
Auto
40
restart
01
Disable
00
Super low
Cool Air
43
Prevention
Follow the
setting on
01
the remote
controller
00
Start/Stop
External
Emergency
46
01
control
stop
02
Forced stop
00
All
Error re-
47
Display only on
port target
01
central remote
controller
Follow the
setting on the
Fan set-
00
remote control-
ting when
ler
cooling
49
thermostat
OFF
01
Stop
7.4.1. Button name and function
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
Default
Details
○
Adjust the heat air trigger temperature.
To lower the trigger temperature by
11 degrees F (6 degrees C), use setting
01. To lower the trigger temperature by
7 degrees F (4 degrees C), use setting
02. To raise the trigger temperature,
use setting 03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency
function such as for power failure
etc.
Do not start and stop the indoor
unit by this function in normal
operation.
○
Be sure to operate by the control
unit, converter or external input
device.
○
Restrain the cold airfl ow with making
the airfl ow lower when starting
heating operation. To correspond to
the ventilation, set to 01.
○
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
○
Change the target for reporting er-
rors. Errors can either be reported in
all locations, or only on the central
remote controller.
When set to 01, the fan stops when
○
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type or
3-wire type) and switching its therm-
istor are necessary.
MANUAL AUTO button
7.4.2. Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION
ON
indicator
lamp (Green)
OFF
TIMER
ON
indicator
0.5s 0.5s 0.5s 0.5s
lamp (Orange)
OFF
ON
FILTER
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator
OFF
lamp (Red)
• Indoor unit address example Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator
1.0s
1.0s
1.0s
lamp (Green)
OFF
TIMER
ON
indicator
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
lamp (Orange)
OFF
ON
FILTER
indicator
OFF
lamp (Red)
• Setting details
Function number
Item
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "7.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function : 31, Setting number : 2
OPERATION
ON
indicator
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
lamp (Green)
OFF
TIMER
ON
indicator
0.5s 0.5s
lamp (Orange)
OFF
ON
FILTER
0.5s
0.5s
0.5s
0.5s
indicator
OFF
lamp (Red)
Indication pattern
Indoor unit
Refrigerant address
address
ON
Flash (1.0s ON/1.0s OFF)
Address: tens place (0.5s ON/0.5s OFF)
Address: ones place (0.5s ON/0.5s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Setting number
00 to 63
00 to 99
Indication pattern
Function number; tens place
(0.5s ON/0.5s OFF)
Function number; ones place
(0.5s ON/0.5s OFF)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
1 cycle 12 sec
9 sec
11 sec
10 sec
En-14