AirStage AGHE007GCAH Manuale di installazione - Pagina 12
Sfoglia online o scarica il pdf Manuale di installazione per Condizionatore d'aria AirStage AGHE007GCAH. AirStage AGHE007GCAH 15. Indoor unit (floor type)
Anche per AirStage AGHE007GCAH: Manuale operativo (8 pagine)
7.4.1 Indoor unit indicator lamps
7.4.2 Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
ON
OPERATION indicator
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Red)
OFF
• Refrigerant address example
(Example) ADDRESS : 30
ON
OPERATION indicator
1.0s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
(Red)
OFF
• Setting details
Function number
01
02
For use with a remote controller, set all rotary switches to 0, and refer to "7.2. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function : 31, Setting number : 2
OPERATION indicator
ON
0.5s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
0.5s
(Red)
OFF
En-11
TIMER lamp
OPERATION
(orange)
lamp (green)
Indication pattern
Indoor unit address
Refrigerant address
ON
Flash (1.0s ON/1.0s OFF)
Address: tens place (0.5s ON/0.5s OFF)
Address: ones place (0.5s ON/0.5s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Item
Setting number
Indoor unit address
00 to 63
Refrigeration address
00 to 99
Indication pattern
Function number; tens place (0.5s ON/0.5s OFF)
Function number; ones place (0.5s ON/0.5s OFF)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
1 cycle 12 sec
0.5s
0.5s
0.5s 0.5s 0.5s
9 sec
11 sec
10 sec
0.5s
0.5s
0.5s
7.5. External input and external output (Optional parts)
7.5.1 Control cover removal
(1) Remove the control cover.
(2) Remove the control inner cover.
(3) Slide out the controller PCB.
FILTER lamp
(red)
7.5.2 Connector positions
DIP switch
(SET 2)
ON
1.0s
7.5.3 External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
*1: Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a: The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
Control cover
Output terminal
(CNA01)
Apply voltage
terminal
(CNB01)
OFF
SW4
SW3
SW2
SW1
DC power supply
12 to 24V
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
Connected unit
Controller
PCB
Control
inner cover
(CNA03)
Controller
PCB
Dry contact
terminal
(CNA04)
(CNA02)
P.C.B
*1
CNA01
*b
CNA03