AirStage ARUL14RLAV Manuale di installazione - Pagina 13

Sfoglia online o scarica il pdf Manuale di installazione per Condizionatore d'aria AirStage ARUL14RLAV. AirStage ARUL14RLAV 20. Indoor unit (duct type)
Anche per AirStage ARUL14RLAV: Manuale operativo (8 pagine)

AirStage ARUL14RLAV Manuale di installazione

6.3. Unit wiring

Before attaching the cable to terminal block.
6.3.1 Power supply cable
Adjust the length of power supply cable to avoid excessive tension with referring fi gure
below.
For U.S.A. and Canada
31/32 in.
(25 mm)
Earth (Ground)
31/32 in.
wire
(25 mm)
For Others
19/32 in. (15 mm)
Earth (Ground)
1-3/16 in. (30 mm)
wire
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping
it around the end of the cable.
(2) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fi x 2 power supply cables with 1 screw.
Strip 31/32 in.
(25 mm)
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
When using solid core cables, do not use the ring terminal. If you use the solid core
cables with the ring terminal, the ring terminal's pressure bonding may malfunction and
cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an
appropriate tool so that the cables do not come loose.
(3) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fi x 2 power supply cables with 1 screw.
Strip 13/32 in.
(10 mm)
Screw with
special washer
Cable
Ring terminal
Terminal block
2-3/16 in.
Conduit connector
(55mm)
2-3/8 in.
(60mm)
Loop
Screw with
special washer
Cable end (Loop)
Cable
WARNING
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
WARNING
Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the unit.
Tightening torque
M4 screw
(Power supply/L1, L2 (N), GND)
6.3.2 Transmission and Remote controller cable
Transmission cable
Shielded wire
(no fi lm)
Remote controller cable
• Connect remote controller and transmission cables as shown in Fig. A.
Fig. A
Good
Prohibited
Different diameter
WARNING
Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
Terminal number
M3 screw
(Transmission/X1, X2)
(Remote controller/Y1, Y2, Y3)
To peel the fi lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an under tightened screw can cause faulty contact,
which will lead to a communication failure.

6.4. Connection of wiring

(1) Remove the cover.
(2) Connect the connection cable.
11 to 16 lbf·in
(1.2 to 1.8 N·m)
31/32 in. (25 mm)
1-9/16 in. (40 mm)
25/32 in. (20 mm)
Prohibited
Connect to 1 side
Tightening torque
4.4 to 5.3 lbf·in
(0.5 to 0.6 N·m)
CAUTION
Screw
Cover
En-12