AirStage AUUB18TLAV Manuale di installazione - Pagina 14
Sfoglia online o scarica il pdf Manuale di installazione per Condizionatore d'aria AirStage AUUB18TLAV. AirStage AUUB18TLAV 17. Indoor unit (cassette type)
Table A
Rotary Switch
Address
Setting
REF AD SW
Refrigerant
circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting range
Remote controller
0 to 15
address
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically confi gured, you do not
need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the remote
controller. For details, please refer to the remote controller manual.
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
En-13
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
6
2
3
4
5
6
A
B
C
D
E
10
11
12
13
14
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2, referring to the Table B.
× 1
0
1
2
3
4
5
6
7
8
9
0
1
2
.
.
.
Table B
3
DIP switch SET 3 SW1
DIP switch SET 3 SW2
7.3. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit ad-
dress settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Filter indica-
tor interval
7
7
F
15
Filter indica-
tor action
Ceiling
airfl ow
Vertical
airfl ow
direction
Cool air
temperature
trigger
Heat air
temperature
trigger
Auto restart
ON
DIP switch "SET 3"
OFF
SW
SW
SW
SW
1
2
3
4
A (Factory setting)
OFF
OFF
Function
Setting number
Default
number
○
00
Standard
11
01
Longer
02
Shorter
○
00
Enable
01
Disable
13
Display only on
02
central remote
controller
○
00
Standard
20
01
High Ceiling
○
00
Standard
23
01
Raise
○
00
Standard
30
01
Adjust (1)
02
Adjust (2)
○
00
Standard
01
Adjust (1)
31
02
Adjust (2)
03
Adjust (3)
00
Enable
40
○
01
Disable
Custom code
B
C
D
ON
OFF
ON
OFF
ON
ON
Details
Adjust the fi lter cleaning interval
notification. If the notification
is too early, change to setting
01. If the notifi cation is too late,
change to setting 02.
Enable or disable the fi lter indi-
cator. Setting 02 is for use with
a central remote controller.
Regulate the airfl ow according
to the needs of the installation
location. When set to 01, the air
fl ow will be stronger. (Cassette
type only)
Adjust the vertical airfl ow direc-
tion. All airfl ow direction louvers
are adjusted together.
(Cassette type only)
Adjust the cool air trigger tem-
perature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature,
use setting 02.
Adjust the heat air trigger tem-
perature. To lower the trigger
temperature by 11 degrees F (6
degrees C), use setting 01. To
lower the trigger temperature by
7 degrees F (4 degrees C), use
setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic
system restart after a power
outage.