AirStage UTY-DCGG Manuale di installazione - Pagina 10

Sfoglia online o scarica il pdf Manuale di installazione per Telecomando AirStage UTY-DCGG. AirStage UTY-DCGG 11. Central remote controller
Anche per AirStage UTY-DCGG: Manuale di installazione (9 pagine)

(7)
Install the screw (1 pc) and fix the panels
61 61

External Input/Output function

For connection cables, use the specified optional parts.
6. 6. 1
External input function
This function performs "Emergency stop" or "Batch
start/stop(All On/All Off)" by using the signal to be input
externally at external input terminals.
There are 2 kinds of input method of External input
terminal: "Dry contact" or "Apply voltage contact".
6. 6. 2
Dry contact
When a power supply is unnecessary at the input
device you want to connect, connect the connection
cables to CN6 and CN7.
*1
*
Do not use the connectors other than specified connectors.
*1.
Short circuit detection resistance (R ON) : ≤ 500 (ohm).
Open circuit detection resistance (R OFF) : ≥ 100 (kilo-
ohm).
*
A twisted pair cable (0.33mm
Maximum length of cable is 25 m (82ft.).
Input Method
Terminal
Edge
CN6
CN6
Pulse
CN7
For "Operation" and "Input method" switching, perform
the settings by "External Input Setting" of menu opera-
tion.
For details of setting method, refer to the operating
manual.
"Operation"
"Input Method"
En-9
PCB
CN7
(Green)
CN6
(White)
2
(22AWG)) should be used.
Input signal
Operation
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
High→Low
or "All Off"
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
Low→High
or "All Off"
"Emergency Stop"
"All On/All Off" (Bach start/stop)
"Edge"
"Pulse"
6. 6. 3
Apply voltage contact
When a power supply must be provided at the input
device, connect the connection cables to CN11 and
CN12.
*2
DC power
supply 24V
*4
*3
*4
*
Do not use the connectors other than specified connectors.
*2.
Make the power supply 24V. Select a power supply ca-
pacity with an ample surplus for the connected load.
*3.
Do not impress a voltage exceeding 24V across pin 1, 3.
*4.
The allowable current is DC5mA or less. (Recommended
DC5mA)
Provide a load resistance such that the current becomes
DC5mA or less.
A twisted pair cable (0.33mm
Maximum length of cable is 25 m (82ft.).
Input Method
Terminal
Edge
CN11
CN11
Pulse
CN12
For "Operation" and "Input method" switching, perform
the settings by "External Input Setting" of menu opera-
tion.
For details of setting method, refer to the operating
manual.
"Operation"
"Input Method"
6. 6. 4
External output function
DC power
supply 12V
-
+
Connect-
ed load *2
+
-
Connect-
ed load *2
connected unit
PCB
CN11 (White) CN12 (Green)
2
(22AWG)) should be used.
Input signal
Operation
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
High→Low
or "All Off"
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
Low→High
or "All Off"
"Emergency Stop"
"All On/All Off" (Bach start/stop)
"Edge"
"Pulse"
PCB
+
-
+
-
*3)
4
1
3
2
CN9