Install the rear panel to a wall.
Transmission cable
Screw ×4
(accessories)
(4)
Cut the thin part (gray marked part) at the top of the front panel
with a cutter.
(5)
Connect the connection cable connector to the connector (CN13)
of the front panel PC board.
(6)
Install the front panel to the rear panel.
CN13
(7)
Install the screw (1 pc) and fi x the panels
6. 6.
External Input/Output function
For connection cables, use the specifi ed optional parts.
6. 6. 1
External input function
This function performs "Emergency stop" or "Batch start/stop(All
On/All Off)" by using the signal to be input externally at external
input terminals.
There are 2 kinds of input method of External input terminal: "Dry
contact" or "Apply voltage contact".
En-7
Extension cable
When passing the cable
through the rear hole, do
not cut off the thin part at
the top.
Cutting out
*
When installing the front
panel to the rear panel,
install it carefully so that the
cable is not pinched or the
parts of the circuit board are
not pushed by things project-
ing from the rear panel. The
circuit board parts may be
damaged.
6. 6. 2
Dry contact
When a power supply is unnecessary at the input device you want
to connect, connect the connection cables to CN6 and CN7.
*1
*
Do not use the connectors other than specifi ed connectors.
*1.
Short circuit detection resistance (R ON) : ≤ 500 (ohm).
Open circuit detection resistance (R OFF) : ≥ 100 (kilo-ohm).
*
A twisted pair cable (0.33mm
mum length of cable is 25 m (82ft.).
Input Method
Terminal
Edge
CN6
CN6
Pulse
CN7
For "Operation" and "Input method" switching, perform the settings by
"External Input Setting" of menu operation.
For details of setting method, refer to the operating manual.
"Operation"
"Input Method"
6. 6. 3
Apply voltage contact
When a power supply must be provided at the input device, connect
the connection cables to CN11 and CN12.
*2
DC power
supply 24V
*4
*3
*4
*
Do not use the connectors other than specifi ed connectors.
*2.
Make the power supply 24V. Select a power supply capacity
with an ample surplus for the connected load.
*3.
Do not impress a voltage exceeding 24V across pin 1, 3.
*4.
The allowable current is DC5mA or less. (Recommended
DC5mA)
Provide a load resistance such that the current becomes
DC5mA or less.
A twisted pair cable (0.33mm
Maximum length of cable is 25 m (82ft.).
Input Method
Terminal
Edge
CN11
CN11
Pulse
CN12
PCB
CN7
(Green)
CN6
(White)
2
(22AWG)) should be used. Maxi-
Input signal
Operation
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
High→Low
or "All Off"
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
Low→High
or "All Off"
"Emergency Stop"
"All On/All Off" (Bach start/stop)
"Edge"
"Pulse"
PCB
CN11 (White)
CN12 (Green)
2
(22AWG)) should be used.
Input signal
Operation
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
High→Low
or "All Off"
"Emergency stop" or
Low→High
"All On"
"Emergency stop"reset
Low→High
or "All Off"