Carlin 60200FR Manuale di installazione e istruzioni per l'uso - Pagina 4
Sfoglia online o scarica il pdf Manuale di installazione e istruzioni per l'uso per Controllore Carlin 60200FR. Carlin 60200FR 9. Gas burner primary control
Anche per Carlin 60200FR: Manuale di installazione e istruzioni per l'uso (8 pagine)

* Blocked Vent/Spill Switch Operation: During each run cycle, the BV contacts will be checked beginning
30 seconds after ignition. If the BV contacts open (indicating the spill switch has detected a blocked vent),
the control will shut down the burner. The control will either recycle the burner or will go immediately into
Lockout dependent on the Allowed Recycle setting. The spill switch must be closed within 2 seconds on a
call for heat. If not, it will retry 2 times before control goes into lockout.
NOTE: If using a manual reset blocked vent spill switch, the control will lock out with the display reading BV
Switch Open.
Do not start the burner if the combustion chamber contains gas.
View or Change Control Settings
NOTE: The settings mode cannot be accessed during a run
cycle, the burner must be in standby mode (or lockout) to
enter setup.
To enter the Settings Mode: Press the
simultaneously for 2 seconds. The display will show –
Settings Press
To Exit Hold
To View Current Settings: Press the
through all Setting Modes (see table at the top of page 5 for
Setting Mode options). The second line of the screen will
display the current setting for each Setting Mode –
Pre-Purge
Pressing the
E
button again will leave the setting as is and
move to the next option –
Trial for Ign
Carlin Combustion Technology, Inc.
Jumper
or
Blocked Vent/
Thermostat
Spill Switch*
G
E
and
buttons
E
button to scroll
30 Seconds
4 Seconds
N.O.
Dry
CO Sensor
Contacts
To Change a Setting: Scroll to the desired Setting Mode
E
option using the
button (as described in table on page
H
5), then press the
or
able Settings. When the desired setting is displayed on the
E
/ ENTER button. The display will briefly
screen press the
indicate that the new setting has been "Entered" and the new
setting will replace the previous setting on the second line of
the screen. Continue pressing the
rent setting for all options or
changes.
Trial for Ign
To Exit the Setup Menu: Press the
seconds. NOTE: The control will automatically exit the Setup
menu after 30 seconds of inactivity or by a call for heat.
4
button to scroll through the avail-
E
button to view the cur-
H
button to make any desired
6 Seconds
F
/ ESCAPE button for 3