Set the rotary switches in the OD to the desired address. You only need to
change the address if there is more then (1) refrigerant system in a
communications network.
REF AD MUST BE
BETWEEN A RANGE OF
00 – 63.
A "terminal resistor" is on board of every J-II OU.
DIP switch SET5-4 will enable or disable the onboard terminal resistor.
There must be (1) terminal resistor setting to ON for every network segment.
STAND ALONE J-II SYSTEMS- TURN DIP SWITCH SET 5-4 "ON"
POWER MUST REMAIN OFF WHEN SETTING ALL DIP AND ROTARY SWITCHES.
Refer to the Installation Manual for complete installation details.
Refer to the Installation Manual for complete installation details.
17
Indoor units physically piped together with the outdoor unit MUST HAVE
THE SAME REFRIGERANT ADDRESS.
Please refer to the applicable indoor unit Installation Manual for rotary switch location and setting
details.
ALL INDOOR UNITS ARE SHIPPED WITH A DEFAULT REF AD OF 00.
EXAMPLE REF AD OF 63 IS SHOWN.
6b
19
BEFORE TURNNG ON POWER:
Check the resistance between X1 and X2 at the OU, and compare with the
resistance table below. IF THE RESISTANCE VALUE IS OUT OF RANGE, PLEASE
CONFIRM THE TERMINAL RESISTOR SETTING IN QIG STEP 19.
PLEASE REFER TO THE INSTALLATION
MANUAL FOR COMPLETE TRANSMISSION
LINE WIRING DETAILS!
8
18
19b