Drazice OKC 160 NTR / BP Manuale di funzionamento e installazione - Pagina 10

Sfoglia online o scarica il pdf Manuale di funzionamento e installazione per Caldaia Drazice OKC 160 NTR / BP. Drazice OKC 160 NTR / BP 18. Stationary water heaters
Anche per Drazice OKC 160 NTR / BP: Manuale di funzionamento e installazione (17 pagine), Manuale di funzionamento e installazione (12 pagine), Manuale di funzionamento e installazione (20 pagine), Manuale di funzionamento e installazione (20 pagine), Manuale operativo e di installazione (20 pagine), Manuale di funzionamento e installazione (18 pagine), Manuale operativo e di installazione (13 pagine)

Drazice OKC 160 NTR / BP Manuale di funzionamento e installazione
system. No stop valves can be put between the appliance and the safety valve. During
assembly, follow the guide provided by the safety equipment manufacturer.
It is necessary to check the safety valve each time before putting it into operation. It is
checked by manual moving of the membrane from the seat, turning the make-and-break
device button always in the direction of the arrow. After being turned, the button must click
back into a notch. Proper function of the make-and-break device results in water draining
through the safety valve outlet pipe. In common operation, such a check needs to be
implemented at least once a month, and after each appliance shutdown for more than 5
days. Water may be dripping off the drain pipe of the safety valve; the pipe must be open
into the air, pointed down; environment temperatures must not drop below zero. When
draining the appliance, use the recommended drain valve. First, close the water supply into
the appliance. Find necessary pressure values in the following table. For proper safety valve
operation,
a backflow valve must be mounted on the inlet pipes, preventing spontaneous appliance
draining and hot water penetrating back into the water main.
Required pressures - Table 4. We recommend that the hot water distribution from the appliance was as
short as possible to minimise heat losses.
SAFETY VALVE STARTING
PRESSURE (MPa)
0,6
0,7
1
Table 4
Appliances must be provided with a discharge valve mounted on the cold service water inlet to the
appliance for potential disassembly or repair.
ACCEPTABLE OPERATING OVER-PRESSURE
OF THE APPLIANCE (MPa)
0,6
0,7
1
Figure 1
MAX COLD WATER
PRESSURE IN PIPING (MPa)
up to 0.48
up to 0.56
up to 0.8
O - Air outlet valve
U – Shut-off valve
P1 - Safety valve with backflow flap
P2 - Safety valve for heating circuit
M - Manometer
Z – Test valve
V - Drain valve
- 10 -