Daikin VRVIII-S Series Manuale dei dati tecnici
1
Specifications
1-1 TECHNICAL SPECIFICATIONS
Notes
1-2 ELECTRICAL SPECIFICATIONS
(50HZ)
Power Supply
Name
Phase
Frequency
Voltage
Current
Minimum circuit amps (MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
1-3 ELECTRICAL SPECIFICATIONS
(60HZ)
Power Supply
Name
Phase
Frequency
Voltage
Current
Minimum circuit amps (MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PBVE
FXDQ20PBVE
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote control; this pressure means : high static pressure -
The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher
than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction,
FXDQ20PBVE
Hz
V
A
0.8
15
A
0.6
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
Maximum allowable voltage range variation between phases is 2%.
FXDQ20PBVE
Hz
V
A
0.9
15
A
0.7
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
Maximum allowable voltage range variation between phases is 2%.
®
• VRV
Systems • Indoor Units
FXDQ25PBVE
equivalent refrigerant piping : 7.5m (horizontal)
equivalent refrigerant piping : 7.5m (horizontal)
standard static pressure.
sound level will increase
FXDQ25PBVE
VE
1~
50
220-240
0.8
15
0.6
-10%
+10%
or above listed range limits.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXDQ25PBVE
VE
1~
60
220
0.9
15
0.7
-10%
+10%
or above listed range limits.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
3
FXDQ32PBVE
1
1
FXDQ32PBVE
0.8
15
0.6
FXDQ32PBVE
0.9
15
0.7
3