6.1 Troubleshooting (continued)
Please use caution when troubleshooting or repairing all electrical components. Be certain
that all power is disconnected from the COOL-SPACE
guard are removed to gain access to the fan.
Problem
Fan won't run and makes no
sound.
Fan motor won't run and makes
a humming sound.
Breaker trips or fuse blows when
fan is started.
Motor overheating and shutting
off. Restarting several minutes
later.
Fan motor won't run and switch
makes soft clicking sound.
Fan blade doesn't turn and unit
makes squealing sound.
Fan will not reach speed but
turns and makes humming
sound.
Fan System
unit before the cooling pads or fan
®
Direct Drive Models
Check
Power cord, extension cord, switches,
circuit breaker, GFI ground fault.
Blade in contact with shroud.
Motor stalled (will not turn by hand).
Motor stall.
Check power source for min. 120volt/15
amp. Extension cord.
Extension cord gauge too small.
Inlet air obstructed or too close to
wall.
Faulty motor.
Switch making good contact.
Motor stall (as above).
Capacitor (where visible) and motor
electrical connections. Extension cord to
small.
7
Solution
Reconnect power or
extension cord.
Reset breaker.
Re-center blade
hub.
Replace motor.
Replace motor.
Upgrade power
supply. Replace
with heavier cord.
Replace with
heavier cord.
Provide minimum
3 feet inlet
clearance.
Replace motor.
Replace switch.
Replace motor.
Replace capacitor or
motor.
Increase cord
gauge.