5.
O
PERATION RANGE
Operation range
Use the system in the following temperature and humidity ranges for
safe and effective operation.
RXQ5~18
RXYQ5~18
COOLING
–5~43°C DB
Outdoor temperature
21~32°C DB
Indoor temperature
14~25°C WB
≤80%
Indoor humidity
(*) Range for operation: –20~–15°C WB. Range for continuous operation:
–15~15.5°C WB.
(†) to avoid condensation and water dripping out the unit.
If the temperature or the humidity is beyond these conditions, safety devices may
work and the air conditioner may not operate.
6.
O
PERATION PROCEDURE
Operation procedure varies according to the combination of
outdoor unit and remote controller. Read
operation" on page
2.
To protect the unit, turn on the main power switch 6 hours before
operation.
If the main power supply is turned off during operation, operation
will restart automatically after the power turns back on again.
6.1.
Cooling, heating, fan only, and automatic
operation
(See
figure 3
Changeover cannot be made with a remote controller whose
display shows
(change-over under centralized control).
When the display
flashes, refer to
"6.4. Setting the master remote controller" on
page
4.
RXQ series let you select fan only and cooling operation.
The fan may keep on running for about 1 minute after the
heating operation stops.
The air flow rate may adjust itself depending on the room
temperature or the fan may stop immediately. This is not a
malfunction.
For systems without cool/heat changeover remote control
switch
(See figure 3)
1
Press the operation mode selector button several times and
select the operation mode of your choice.
Cooling operation
Heating operation
Fan only operation
2
Press the on/off button.
The operation lamp lights up and the system starts operation.
RX(Y)Q5~18P7W1B + RXYQ8~18P7W1B1 + RXYSQ4~6P7V3B
VRVIII and VRVIII-S system air conditioner
4PW28160-1A
RXYSQ4~6
COOLING
HEATING
–5~46°C DB
–20~24°C DB
–20~15.5°C WB
21~32°C DB
15~27°C DB
14~25°C WB
(†)
≤80%
(†)
≤80%
"2. What to do before
and
figure
4.1)
(change-over under centralized control)
For systems with cool/heat changeover remote control switch
1
Select operation mode with the cool/heat changeover remote
control switch as follows:
(*)
2
Press the on/off button.
The operation lamp lights up and the system starts operation.
Adjustment
(†)
For programming temperature, fan speed and air flow direction, refer
to the operation manual of the remote controller.
Stopping the system
3
Press the on/off button once again.
The operation lamp goes off and the system stops operation.
NOTE
Do not turn off power immediately after the unit stops,
but wait for at least 5 minutes.
Explanation of heating operation
It may take longer to reach the set temperature for general heating
operation than for cooling operation.
The following operation is performed in order to prevent the heating
capacity from dropping or cold air from blowing.
Defrost operation (heat pump and heat recovery types only)
In heating operation, freezing of the outdoor unit coil increases.
Heating capability decreases and the system goes into defrost
operation.
The indoor unit fan stops and the remote controller displays
.
After maximum 10 minutes of defrost operation, the system
returns to heating operation again.
Hot start (heat pump and heat recovery types only)
In order to prevent cold air from blowing out of an indoor unit at
the start of heating operation, the indoor fan is automatically
stopped. The display of the remote controller shows
It may take some time before the fan starts. This is not a
malfunction.
NOTE
Cooling operation
(figure
4.1)
Heating operation
(figure
4.2)
Fan only operation
(figure
4.3)
The heating capacity drops when the outside
temperature falls. If this happens, use another
heating device together with the unit. (When using
together with appliances that produce open fire,
ventilate the room constantly.)
Do not place appliances that produce open fire in
places exposed to the air flow from the unit or
under the unit.
It takes some time to heat up the room from the
time the unit is started since the unit uses a hot-air
circulating system to heat the entire room.
If the hot air rises to the ceiling, leaving the area
above the floor cold, we recommend that you use
the circulator (the indoor fan for circulating air).
Contact your dealer for details.
.
Operation manual