Heat Lockout [AV59] R/W – Heating mild weather stat setting. When
the outside or mixed air temperature is above this setting the burner will be
automatically disabled (only available if the unit has mild weather stat as an
option).
Control Deadband [AV58] R/W - Space temperature deadband for
cycle on/off control.
Discharge Set Pt [AV53] R/W - Discharge temperature set point for
heating mode.
Min Discharge [AV54] R/W – The units minimum allowable
discharge temperature.
Max Discharge [AV55] R/W – The units maximum allowable
discharge temperature.
Low Temp Set Pt [AV56] R/W – If the unit discharges air below this
temperature set point for "Low Temp Time" minutes it will shut down and
close the isolation dampers (Only available if LTL is available).
Low Temp Minutes [AV57] R/W – The time delay (in minutes) for the
"Low Temp Alarm" (Only available if LTL is available).
Advanced Menu (Press and hold "menu" button for 5 seconds to enter)
Date Time
Year – Set the real time clock year.
Date – Set the real time clock date.
Time – Set the real time clock time.