10. Check the direction of flow:
Ensure the sensor elements are aligned correctly with the flow (±2 degrees). Note differences between
•
equal and unequal sensor types.
Insertion type flow meters: Is the arrow on the flow meter probe pointing in the direction of flow?
•
Inline type flow meters: An inline meter will have the flow direction arrow on both the probe and flow
•
body. Are both arrows pointing in the direction of flow?
11. What is the CSV voltage?
Press the F1 & F2 keys at the same time in normal mode to access the engineering displays. Display #10
•
will have the CSV value. Compare this value to the meter's calibration certificate.