Daintree GE current Proline LEX Series Manuale di installazione - Pagina 4

Sfoglia online o scarica il pdf Manuale di installazione per Apparecchiature di illuminazione Daintree GE current Proline LEX Series. Daintree GE current Proline LEX Series 5. Exit sign

Daintree GE current Proline LEX Series Manuale di installazione
Proline® LEX Series Exit Sign

Conduit Entry

FLEXIBLE CONDUIT ONLY!
Operation (Battery Back-up)
1
Apply AC power to the unit. The LED indicator will be RED. Plug battery into the board and the LED indicator
will turn Green.
  2
After the battery has been left to charge for 2 hours, test the unit by pushing the switch. The LED indicator
turns OFF and the LED board stays ON.
  3
When the switch is released, the LED indicator will turn to GREEN and the LED board remains ON.
1
Drill a 3/4" hole through the desired conduit entry knockout
location on the top or side of the frame of the sign.
2
Route the AC input conduit into housing.
3
All conduit connections must use UL LISTED and SUITABLE
FOR WET LOCATION parts.
4
To finish installation of EXIT sign, reference Wall, Ceiling
or End Mount instructions.
4
Installation Guide