Daintree GE Current WOS2-WM Manuale di installazione - Pagina 3
Sfoglia online o scarica il pdf Manuale di installazione per Accessories Daintree GE Current WOS2-WM. Daintree GE Current WOS2-WM 4. Wireless occupancy sensor
Daintree
Networked Wireless Occupancy Sensor (WOS2-WM)
®
3
Placement (continued)
The sensor is
most responsive
when crossing
the field
of view:
The sensor
is less responsive
to radial
movement:
MORE
RESPONSIVE
WOS2-WM-W (wide-angle)
Installation Height
Installation Angle
Detection Angle
Detection Range
WOS2-WM-L (long range)
Installation Height
6.5' to 7.2' (2m to 2.2m) from floor
Installation Angle
15° tilt toward floor
Detection Angle
20° / 30 meters
6.5' to 98.4' (2m to 30m)
Detection Range
LESS
RESPONSIVE
6.5' to 10' (2m to 3m) from floor
15° tilt toward floor
110°
up to 36' (11m)
4
Adjustments
Two trimpots on the back of the sensor are used to adjust
the Daylight Hold-Off threshold and PIR motion sensor
sensitivity. For easier access to the trimpots after the sensor has
been mounted, remove the sensor from the mounting bracket.
Remove
sensor
from
bracket
Attach
sensor
to
bracket
Use caution when adjusting the trimpots. Do not use excess
force, as this will damage the unit. Stop turning the trimpot when
you feel resistance.
5
PIR Sensitivity
Turn the trimpot clockwise to increase
sensitivity. Turn the trimpot counter-clockwise
to decrease sensitivity.
To test the daylight hold-off after the installation is complete
and the sensor has been added to CSM:
1. Ensure that the DCS control strategy for this zone makes
use of occupancy sensors and has the 'Enable Daylight
hold-off ' check box selected.
2. Wait until vacancy is detected and the lights turn off.
3. Trigger occupancy while the light level is below the selected
threshold. The lights should turn on. Trigger occupancy while
the light level is above the selected threshold. The lights
should remain off.
3
Installation Guide
Maximum
Minimum
(clockwise)
(counter-clockwise)