FoxESS EPS Box-TP Manuale d'uso - Pagina 10
Sfoglia online o scarica il pdf Manuale d'uso per Accessories FoxESS EPS Box-TP. FoxESS EPS Box-TP 16.
Step 4: Install the expansion screws with screwdriver to fix the EPS Box-TP.
4. Wiring Connection
Step1: Grid String Connection
EPS Box-TP is designed for three-phase grid. Per voltage range is 220/230/240V; frequency is
50/60Hz. Other technical requests should comply with the requirement of the local public grid.
Model(kw)
Cable (Load)
Cable (ON-GRID) 4.0mm
Cable (EPS)
Micro-Breaker
Step 2: Grid Wiring
•
Check the grid voltage and compare with the permitted voltage range (refer to technical data).
•
Disconnect the circuit-breaker from all the phases and secure against re-connection.
•
Trim the wires:
-Trim all the wires to 52.5mm and the PE wire to 55mm.
-Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
Note: Please refer to local cable type and color for actual installation
EPS Box -TP Series User Manual
5.0
6.0
6.0mm
6.0mm
2
2
4.0mm
2
2
4.0mm
2
4.0mm
2
32A
32A
L1/L2/L3: Brown/Red/Green or Yellow Wire
N: Blue/Black Wire
PE: Yellow & Green Wire
www.fox-ess.com
8.0
10.0
6.0mm
6.0mm
2
2
4.0mm
4.0mm
2
2
4.0mm
2
4.0mm
2
32A
32A
12.0
6.0mm
2
4.0mm
2
4.0mm
2
32A
P a g e | 6