• REMOTE CONTROL OUTPUTS
DSE7300 and DSE8000 series have the option of configuring outputs, expansion outputs and LEDs to Remote
Control sources.
Remote control outputs are controlled by writing 0 (off) or 1 (on) to the following Gencomm registers.
Modbus page 193 (Address C100 Hex) (49408 decimal) and the following 9 registers:
Hex address
Decimal address
C100
49408
C101
49409
C102
49410
C103
49411
C104
49412
C105
49413
C106
49414
C107
49415
C108
49416
C109
49417
056-051 Gencomm Control Keys Issue 3 – A.D.Manton
Example of configuration to Remote Control in DSE Config Suite Software
Output
Remote Control Output 1
Remote Control Output 2
Remote Control Output 3
Remote Control Output 4
Remote Control Output 5
Remote Control Output 6
Remote Control Output 7
Remote Control Output 8
Remote Control Output 9
Remote Control Output 10