B. AC Input Characteristics
1. Input Frequency: 60 Hz
2. Power walk-in: 0 to 100% over a 10-second period.
3. Magnetizing Inrush Current: Less than nominal input current for less than one cycle.
4. Input Surge Protection: The UPS is equipped with standard input filter assembly will with-
stand surges per IEEE 587-1980/ANSI C62.41
AC Output Characteristics
1. Voltage Regulation: + 3.0% for no-load to full load and complete 10 minute battery run mode.
2. Frequency: 60 Hz (+ 0.1Hz when free running).
3. Voltage Distortion: Maximum 5% total (THD) @ 100% linear loads.
4. Voltage Transient (Step Load) Response:
a. + 5% for 50% step load change
b. + 8% for 100% step load change
c. + 3 for loss or return of AC input power or manual transfer at full load.
5. Voltage Recovery Time: Return to within 3% of nominal value within 50 milliseconds.
6. Non-Linear Load Capability: Output voltage total harmonic distortion shall be less than 8%
when connected to a 100% non-linear load with a crest factor not to exceed 2.5%.
7. Slew Rate: 1 Hz/second maximum
8. Power Factor: Unity power factor.
9. Inverter Overload Capability:
a. 125% of rated load for 1 minute
b. 145% of rated load for 10 seconds
10. Bypass Overload Capability: > 200% for one cycle; > 150% for 30 seconds
11. (LCD Monitor only) Every 30 days a self testing / self-diagnostics will be activated. The sys-
tem will log (store in memory) any alarms and make available through the front panel LCD all
information. The RS 232 / 485 will also make information available. The system will monitor all
working parameters before, during and after testing.