Auber TD100 Manuale di istruzioni - Pagina 2

Sfoglia online o scarica il pdf Manuale di istruzioni per Regolatore di temperatura Auber TD100. Auber TD100 3. Temperature controller

AUBER INSTRUMENTS
5. Parameter Settings
To change the target temperature, press SET key momentarily. The
controller will show CSP (Cooling set point), press SET again will
show HSP (heating set point). When the controller shows CSP or
HSP, use Up or Down key to change the value. Then press SET key
to confirm the change.
To change the system parameters, press SET key for 5 seconds, the
controller will enter the parameter set up mode. The first parameter
AH will show on the display. Use Up or Down key to modify the
parameter value. Then press SET key to confirm the change. The
display will show the parameter again. Press the SET key to show
the next parameter. The instrument will automatically exit if no key is
pressed for 10 seconds. Please see the Table 1 for the parameters.
Table 1. Parameters Description
Code
Description
CSP CSP
Cooling Set Point
HSP HSP
Heating Set Point
AH AH
Alarm High Limit
AL AL
Alarm Low Limit
CdF CDF
Cooling Differential
HdF HDF
Heating Differntial
AS AS
Cooling Antishort
SFA SFA
Sensor Failure Operation
oFS OFS
Temperature Offset
C-F C-F
Temperature Unit
Note 1.
For cooling (or heating), the output will be off when the
temperature is blow (or over) the set point; will be on again when the
temperature rises up (or drops down) to CSP+CdF (or HSP-HdF).
The maximum value of the HSP can be set is the current value of
CSP. But CSP can be set to the value between -58~248 ºF or
-50~125 ºC. When the CSP is set to a value lower than current HSP,
the HSP will be adjusted to the CSP value automatically.
For example, when CSP=67.0 ºF, HSP=62 ºF, HSP can be set to any
value between -58 and 67.0. For CSP, it can be set to any value
between -58 and 248. If you set it to 55.0, the HSP will be set to 55.0
automatically.
Small differential gives tight control; large differential reduces the
frequency of cycle on and off. It will extend the life of relay and
compressor.
2013.05
Note 2.
limit alarm will be on; when the measured temperature is lower than
AL, the low limit alarm will be on.
When alarm is on, the display will be flashing between the measured
value and alarm type. To mute the alarm when it is on, press the
Down key momentarily. If the measured value gets out of the alarm
zone then gets back to the alarm zone again, the alarm will be on
again. To disable the alarm, set AH=AL.
The maximum value of the AL can be set is the current value of AH.
But AH can be set to the value between -58~248 ºF or
-50~125 ºC. When AH is set to a value lower than current AL, the AL
will be adjusted to the AH value automatically.
For example, when AH=95.0 ºF, AL=32 ºF, AL can be set to any
Setting range
Initial Note
value between -58 and 95.0. For AH, it can be set to any value
-58~248 ºF
between -58 and 248. If you set it to 25.0, the AL will be set to 25.0
67.0
-50~125 ºC
automatically.
1
-58~CSP ºF
62.0
-50~CSP ºC
Note 3.
-58~248 ºF
95.0
cooling load on.
-50~125 ºC
2
compressor, it should not turn on the compressor when it is at high
-58~AH ºF
32
pressure (just after turned off). Otherwise, It may shorten the life of
-50~AH ºC
compressor. The Anti-Short cycle delay function can be used to
prevent the rapid cycling of the compressor. It establishes the
0~50.0 ºF
3.0
minimum time that the NO contacts remains open (after reaching
1
cutout) before closing again. The delay overrides any Load Demand
0~50.0 ºF
1.0
and does not allow the NO contacts to close until the set time-delay
value has elapsed. It gives time to release the refrigerant pressure
0~12 min
0
3
through evaporator. It is typically set to 4- 6 (minutes).
0-0, 0-1, 1-0
0-0
4
Note 4.
It can be set to 0-0, 0-1 or 1-0. Please refer to table 2 for details.
0~10.0
0
5
C: Celsius
Table 2. Output of the controller when sensor fails:
F
F:Fahrenheit
For example, when the unit controls a refrigerator for food, you may
want to set the TSF to ON if the sensor fails to keep the food cold.
When it controls a heater, you may want to set the output to OFF for
safety purpose .
Note 5.
error produced by the sensor or input signal itself.
For example, for temperature, if the unit displays 37 ºF when the
actual temperature is 32 ºF, setting parameter toF= - 5 will make the
controller display 32 ºF.
6. How to install the sensor to the unit.
The connector of sensor contains a slot for correct pin connection. It
also has a spring lock to prevent disconnections from accidental
pulling on the cable. To install the to the unit, please align the slot of
WWW.AUBERINS.COM
When the measured temperature is higher than AL, the high
The Cooling Antishort is the delay the time to turn the
w
hen the controller is used for cooling and load is a
The SFA defines how the output would be if the sensor fails.
SFA
Controller output when sensor fails
0-0
cooler off, heater off
1-0
cooler on, heater off
0-1
cooler off, heater on
The offset is used to set an input offset to compensate the
P2/3