AuCom CSX-110 Manuale d'uso - Pagina 12

Sfoglia online o scarica il pdf Manuale d'uso per Controllore AuCom CSX-110. AuCom CSX-110 12.
Anche per AuCom CSX-110: Manuale d'uso (13 pagine)

SPECIFICATIONS
Outputs
Main contactor (terminals 13, 14) ................................................................................................ Normally open
..................................................................................................................... 6 A, 30 VDC / 6 A, 250 VAC resistive
Run relay (terminals 23, 24) ............................................................................................................... Normally open
..................................................................................................................... 6 A, 30 VDC / 6 A, 250 VAC resistive
Environmental
Degree of Protection CSX-007 to CSX-055 ................................................................................................ IP20
Degree of Protection CSX-075 to CSX-110 ................................................................................................ IP00
Operating temperature ............................................................................................................. - 10 °C to + 60 °C
Storage temperature ..................................... -25 °C to + 60 °C (to +70 °C for less than 24 hours)
Humidity ....................................................................................................................... 5% to 95% Relative Humidity
Pollution degree ............................................................................................................................. Pollution Degree 3
Vibration ........................................................................................................................ IEC 60068 Test Fc Sinusoidal
............................................................................................................... 4 Hz to 13.2 Hz: ± 1 mm displacement
........................................................................................................................................... 13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC) ......................................................................................................................................... Class B
Conducted radio frequency emission .................................. 0.15 MHz to 0.5 MHz: < 56-46 dB (μV)
............................................................................................................................ 0.5 MHz to 5 MHz: < 46 dB (μV)
............................................................................................................................. 5 MHz to 30 MHz: < 50 dB (μV)
Radiated radio frequency emission ............................................ 30 MHz to 230 MHz: < 30 dB (μV/m)
............................................................................................................ 230 MHz to 1000 MHz: < 37 dB (μV/m)
EMC Immunity
Electrostatic discharge ............................................................... 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field .................................... 0.15 MHz to 1000 MHz: 140 dB (μV)
Rated impulse withstand voltage (Fast transients 5/50 ns) . 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ........................................... 100 ms (at 40% nominal voltage)
Harmonics and distortion ......................................................... IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit
Rated short-circuit current CSX-007 to CSX-022 ................................................................................. 5 kA
Rated short-circuit current CSX-030 to CSX-110 .............................................................................. 10 kA
1
These short circuit ratings are with fuses used as given in the table under
page 10.
Heat Dissipation
During Start ............................................................................................................................................ 3 watts / ampere
During Run ................................................................................................................................................ 10 watts typical
Standards Approvals
C
.................................................................................................................................................................... IEC 60947-4-2
CE ...................................................................................................................................................................... IEC 60947-4-2
CCC ....................................................................................................................................................................... GB 14048.6
EAC .................................................................................................................. TP TC 004/2011, TP TC 020/2011
Marine .................................................................................................................. Lloyds Marine No 1 Specification
UL / C-UL .................................................................................................................................................................... UL 508
Operational Life
CSX-007~055 ............................................................................................................................ 1,000,000 operations
CSX-075~110 ................................................................................................................................... 30,000 operations
12
CSX User Manual
Semiconductor Fuses
È710-02407-00J*ËÍ
7 1 0 - 0 2 4 0 7 - 0 0 J
710-02407-00J
1
1
on