Before activating air calibration mode:
• Close all windows and doors�
• Ensure that all duct openings in the DucoBox are fully closed and that the
DucoBox cover is closed!
2
• Avoid air leaks in the ventilation ducts�
• Set all window ventilators to the open position� Any Tronic ventilators will open
automatically�
Pull the plug out of the socket and wait a few seconds�
3
Put the plug back into the socket� The DucoBox will be configured automatically on
4
start-up� Calibration takes 30 seconds + 1 minute per connected control valve�
* Depending on the software version of the User controller / CO
08.B Checking
The steps set out below can be used to check whether flow rates have been set correctly�
Checking configured flow rate
Open the DucoBox cover�
1
Press 'HIGH' briefly� The DucoBox will remain in configuration mode for 30 min-
2
utes (as standard)�
Close the cover�
3
Wait at least one minute to allow the ventilation system to stabilise�
4
Measure the vents� If a flow rate differs from the desired output, this can be ad-
5
justed via the display menu or using the Duco Network Tool�
If you finish before the standard setting of 30 minutes, re-open the DucoBox cover
6
and press 'HIGH' again� Then replace the cover on the DucoBox�
16
L2000631 Installation guide for DucoBox Focus (Revision K | 13.07.2020)