DuctSox OvalSox Manuale di installazione - Pagina 7

Sfoglia online o scarica il pdf Manuale di installazione per Cavi e connettori DuctSox OvalSox. DuctSox OvalSox 12.

DuctSox
®
Step 3 – Installation
Determine placement of cable (both cable path and elevation). The cable must be located X inches apart and 1 in (25 mm)
above the 12:00 location of the DuctSox (match this up to the chart and the drawing). Intermediate cable supports are spaced
no more than 12.5 ft (3810 mm).
OvalSox Size
inches
mm
Cable Spacing
inches
mm
T's
There should be roughly 12 in (305 mm) from sidewall of DuctSox to the closest edge of any knee-bracing. Structure too close
to the main run may cause premature failure due to abrasion from the structure.
Publication: AMEN00416 2021-02-22
24
26
28
30
610
660
711
762
35.8
38.7
41.6
44.6
909
983
1057
1133
32
34
36
38
813
864
914
965
47.5
50.4
53.3
56.2
1207
1280
1354
1427
Cable Spacing
12 in (305 mm)
minimum
OvalSox
Installation Manual
40
42
44
46
1016
1067
1118
1168
59.2
62.1
65.0
67.9
1504
1577
1651
1725
12 in (305 mm)
minimum
Cable
48
1219
70.8
1798
7