[How to Use the Filter]
In a power supply system from a certain power source, if the total length of DP, DN, 24V and 0V lines in parallel connection exceeds 50m, the
ASLINK lter ANF-01 should be connected in series to the 24V and 0V terminals at a position where the parallel connection starts.
This lter should be inserted in both cases: batch power supply from a power source for the master unit, and power supply from a local power
source.
To ensure conformity to the CE standard, insert the ANF-01 filter regardless of the distance of lines
in parallel connection.
■Connection example
①Power supply to the entire system
AnyWireASLINK master
DP
POWER IN
DN
24V
0V
LG
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
② Local power supply/branching
AnyWireASLINK master
DP
POWER IN
DN
24V
0V
LG
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
SLAVE
24V
24V
0V
0V
PE
ANF-01
If the total length of the section where all the DP, DN, 24V, and 0V lines run in parallel is more than 50m
2-wire
4-wire
terminal
terminal
SLAVE
24V
24V
0V
0V
PE
ANF-01
If the total length of the
section where all the
DP, DN, 24V, and 0V
lines run in parallel is
more than 50m
2-wire
terminal
POWER IN
SLAVE
L
24V
24V
24V
N
0V
0V
0V
FG
PE
ANF-01
24V DC
stabilized
power supply
General-purpose power
supply lter
(Use it if necessary.)
-ANF01 3/4-
2-wire
4-wire
terminal
terminal
4-wire
4-wire
terminal
terminal
A
4-wire
terminal
B
If the total length of the sections (A + B)
where all the DP, DN, 24V, and 0V lines
run in parallel is more than 50m
4-wire
terminal
DP
DN
Terminator
4-wire
terminal
DP
DN
Terminator
4-wire
terminal