TTS/TGS/TTH/TGH Spare Part Instructions
KIT BEARING SENSOR CABLE ASSEMBLY
100064, 100065.
Installation and servicing of Danfoss Turbocor® compressors by qualified and product trained personnel only.
Follow these instructions and sound refrigeration/electrical/servicing practices relating to installation,
commissioning, maintenance and service.
Consult the appropriate
Danfoss Turbocor
Compressors Inc. (DTC)
Service Manual on
turbocor.danfoss.com for
detailed service instructions.
1 - Introduction
BEARING SENSOR CABLE ASSEMBLY replacement.
This kit contains the Bearing Sensor Cable Assembly. Please refer to our Service Manual for details regarding the
replacement of the cable.
We have made the TTS/TGS/TTH/TGH Service Manual available to anyone. To access the manual, you may scan the
applicable QR code below or you may go to our DTC website at www.turbocoroem.com. At the top of the page there is a
pull-down menu called "Quick Links." Click this menu and select the appropriate service manual.
Refer to the applicable QR code below to download the TTS/TGS/TTH/TGH Service Manual.
English
2 - Front Sensor cable Replacement Procedure:
Removal of old cable:
1) Connect cable to connector (J10) on backplane. See Figure 2. Ensure that plug is inserted in correct polarity.
Refer to locating keys on plug and slots in connector. Snap connector retainers into place by gently
squeezing.
Page 1 of 4
Never power compressor
without covers in place and
secured.
Removing the mains input
cover will expose you to a
voltage hazard of up to 575V.
Ensure the mains input power
is off and locked out before
removing cover.
Before removing top cover,
wait at least 20 minutes after
isolating AC power to allow
the high voltage capacitors to
discharge.
Document number: 700493 REV L
ENGINEERING
TOMORROW
Always wear appropriately
rated safety equipment when
working around equipment
and/or components
energized with high voltage.
This equipment contains
hazardous voltages that
can cause serious injury or
death.
Chinese
© Copyright Danfoss | 2019.05
Recover all refrigerant
from compressor in
accordance with local
codes and ensure pressure
is fully vented before the
removal of refrigerant
containing components.