Danfoss RA 2000 Scheda tecnica - Pagina 7
Sfoglia online o scarica il pdf Scheda tecnica per Termostato Danfoss RA 2000. Danfoss RA 2000 9. One pipe steam thermostatic radiator
Anche per Danfoss RA 2000: Manuale di installazione (2 pagine), Istruzioni per l'installazione (4 pagine)
Data Sheet
Fitting Danfoss radiator
thermostats
Changing the gland seal
DKCD
Radiator thermostats for one-pipe and two-pipe systems
Built-in sensors
are best fitted horizontally so that the ambient air can
pass freely over the sensor without being affected by
heat from valve and possibly surface pipes.
Remote sensors
should be used when:
- curtains cover the sensor
- or the sensor is affected by surface pipes.
- It is necessary to mount the sensor in the vertical
position because of adjacent obstructions and the
valve body is flow mounted.
The remote sensor must be mounted on the wall, away
from curtains, or on the skirting board beneath the
radiator if free of surface pipes. All remote sensors are
now supplied with ultra-thin capillary. Simply pull out
the length required (2m max.) and fix using clips
provided.
Remote temperature adjuster
is ideal for use when the valve is positioned inaccessible
to the user. The temperature adjuster should be
mounted 1.5m above the floor.
IMPORTANT
Do not use RA 2000 sensors with RA-FR reversible
valve bodies.
Should the valve body gland seal shows signs of
weeping, the gland seal can be renewed in a few
minutes with the system in operation.
VD.51.Q1.12 © Danfoss 10/2003
Order gland seal 013U0070 for RAVL and RAV
valves. 013G0290 for RA-FN and RA-G. (Sold in
packs of 10 units, complete with instructions).