Danfoss 080G0325 Manuale d'uso - Pagina 13

Sfoglia online o scarica il pdf Manuale d'uso per Unità di controllo Danfoss 080G0325. Danfoss 080G0325 16. Stepper valve extension module, adap-kool refrigeration control system

Danfoss 080G0325 Manuale d'uso
User Guide | Stepper Valve Extension Module, Type EKE 1P

Connections

ANALOGUE / DIGITAL INPUT
RS-485
ANALOG / DIGITAL INPUT
Stepper Valve Module
Superheat controller
EKE 1P
PWR 24V
Vbat
STEPPER VALVE
STEPPER VALVE
Technical specifications
I/O
Type
Voltage
Analogue inputs
PT1000
Auxiliary
Supplies
Voltage free
Digital inputs
contacts
Digital output
Relay
Bipolar /
Stepper motor
unipolar
Battery backup
RS-485 RTU
Communication
CAN
* Only used in application 1
© Danfoss | DCS (vt) | 2020.03
CAN - RJ
CAN RJ
CAN RJ
DIGITAL OUTPUT
DIGITAL OUTPUT
No.
Specification
Max. 15 V input voltage
Do not connect voltage sources to unpowered units without limiting the current to analogue inputs (overall 80 mA).
Open circuit HW diagnostics available for voltage input on: AI4
AI3*
0 – 5 V ratiometric
2
AI4
0 – 5 V, 0 – 10 V
2
AI1*, AI2*
5 V +
1
Sensor supply: 5 V DC / 15 mA, overload protection approximately 150 mA
DI1*, DI2
Steady current minimum 1mA
Cleaning current 100 mA at 15 V DC
2
On: RIL < = 300 Ω
Off: RIH > = 3.5 k Ω
C1-NO1*
Normally Open: 3 A General purpose, 250 V AC, 100 k cycle
1
Normally Open: 3 A Inductive (AC-15), 250 V AC, 100 k cycle
Normally Closed: 2 A General purpose, 250 V AC, 100 k cycle
Stepper valves: A1, A2, B1, B2
Bipolar and unipolar stepper motor output:
- Danfoss CCMT 3L- CCMT 8L / CCMT 0 – CCMT 42 / CCM 10 - CCM 40/ETS 6 - ETS 400/ CTR 20
Other valves:
- speed 10 – 400 pps
1
- drive mode 1/8 microstep
- max. peak phase current: 1.2 A (848 mA RMS)
- max. drive voltage 40 V
- max. output power 12 W
VBATT: 18 – 24 V DC (24 V DC recommended)
- Leakage: <15 μA @30 V DC
- max. battery current: 850 mA at 18 V
- battery alarm will be activated below 16 V DC
Required power to do one closing of stepper valve:
ETS 6
: 110 J / 30 V mAh
ETS 12.5 - ETS 400
: 60 J / 17 V mAh
1
KVS 15 / KVS 42
: 60 J / 17 V mAh
ETS 12C - ETS 100C
: 55 J / 15 V mAh
KVS 2C / KVS 5C
: 55 J / 15 V mAh
CCMT 2 - CCMT 8
: 60 J / 17 V mAh
CCMT 16 - CCMT 42
: 175 J / 49 V mAh
CCMT 3L - CCMT 8L
: 60 J / 17 V mAh
CTR 20
: 60 J / 17 V mAh
RS-485*
Galvanic isolation
1
No built-in termination
CAN – RJ
Application 1: Connect directly to AK-PC
1
Application 2: Connect directly to graphical display, MMIGRS2. Activate the termination on the graphical display.
Valve connection
CCMT/ETS/CCM
ETS 6
White
Orange
Black
Yellow
Red
Red
Green
Black
Application 1 driver configuration
AI4 open circuit or connected to 0 V (COM): high-pressure valve driver
AI4 connected to 5 V+: receiver valve driver
Recommended wire size and cable distance between
EKE controller and stepper motor valve
Cable length
1 – 15 m
Wire diameter
0.52 / 0.33 mm2 (20 / 22 AWG)
EKE 1P
A1
A2
B1
B2
BC320219567793en-000201 | 13