Dungs DMA Istruzioni per l'installazione

Sfoglia online o scarica il pdf Istruzioni per l'installazione per Controllore Dungs DMA. Dungs DMA 3. Motor actuator, butterfly control valve

Dungs DMA Istruzioni per l'installazione
DMA
Motor Actuator
Installation Instructions
The DMA actuator drives from 0 to 90 degrees via 4-20 mA
input signal. It can move in any direction and stop anywhere
over the entire 90 degree stroke.
Electrical Rating
110-120 Vac (+10 / -15%) 50-60 Hz
Max. Power Rating
2.0 VA Holding, 5.4 VA Operating
Max. Torque Ratings
Timing
6
12
30
Position Resolution
0.08mA resolution; minimum of 0.45° per step
The DMK/6 butterfly control valve actuates from 0 to 90
degrees in either direction; it is not a tight shut-off valve.
Input-side male thread and output-side female thread en-
able assembly directly to DUNGS shutoff valves.
Gases
Natural gas, propane, butane, noncorrosive gases,
and air. Suitable for up to 0.1% by volume, dry H
Max. Pressure
7 PSI (500mbar) MH194167
Max. Differential Pressure
1.5 PSI (100mbar)
• Read these instructions carefully.
• Failure to follow them and/or improper installation may
cause explosion, property damage and injuries.
• Installation must be done with the supervision of a
licensed burner technician.
• Check the ratings in the specifications to make sure that
they are suitable for your application.
• Never perform work if gas pressure or power is applied,
or in the presence of an open flame.
Phone: (651) 792-8912 Fax: (651) 792-8919 Website: www.dungs.com E-mail: [email protected]
1 ... 3
DMK/6
Butterfly Control Valve
Installation Instructions
DMA ACTUATOR SPECIFICATIONS
Holding
Operating
12.4 in-lb
5.3 in-lb
24.8 in-lb
8.9 in-lb
26.5 in-lb
17.7in-lb
DMK BUTTERFLY VALVE SPECIFICATIONS
2
524 Apollo Drive,Suite 10 Lino Lakes, MN 55014 U.S.A.
Industrial Combustion Components
Tel: 804.236.3881 Fax: 804.236.3882 E-mail: [email protected]
Max. Contact Rating for Auxiliary Switch
1.5 Amps at 120 Vac 50/60 Hz
Enclosure Rating
NEMA Type 1 enclosure (standard with DMA)
NEMA Type 4 enclosure avaliable (Part #D240 456)
Input Control
4 to 20 mA
Position Feedback or Slave Output
4 to 20 mA; 500 ohm maximum impedance.
Resistence across terminals 8 & 10 is 250 Ohms.
Ambient Temperature Rating
+15 °F to +120 °F (-10 °C to 50 °C)
Approvals
UL Recognized Component: File No. E142163
CSA Certified: File No.157406-1378915
Commonwealth of Massachsetts Approved Product
Approval code G1-1107-35
Max. Body Pressure
15 PSI (1000mbar)
Mounting Position
Mulitpoised
S.
Ambient Temperature for DMK
+5° F to +140° F (-15° C to 60° C)
Actuator angle
90 degrees from open to closed
Approvals
UL Listed Component: File No. MH18741
Commonwealth of Massachsetts Approved Product
Approval code G1-1107-35
ATTENTION
• Once installed, perform a complete checkout including
leak testing.
• Verify proper operation after servicing.
• The system must be installed, used, and maintaned to
meet all applicable national and local code requirements
such as but not limited to NFPA 86,CSD-1, ANSI Z21.13,
UL 795, NFPA 85, or CSA B149.3.
Karl Dungs, Inc
Burnerparts.com