Danfoss NovoCon XL Manuale operativo - Pagina 6
Sfoglia online o scarica il pdf Manuale operativo per Pompa dell'acqua Danfoss NovoCon XL. Danfoss NovoCon XL 8.
NovoCon® L/XL
❼
®
NovoCon L
003Z8560
Actuator for AB-QM DN125-150
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
Power: 24VAC/DC, 50/60 Hz, Operating 9.6 VA
Force: 2000N. Stroke: 50 mm. Speed: 3-24s/m. IP54/40, 10T55
❽
DIP Switch
1
2
3
4
5
❾
Initial configuration
Application mode:
MSV:9 / 32810
Digital control (default),
Analog control
Application mode:
MSV:9 / 32810
Digital control (default),
Analog control
6 | © Danfoss | 2021.09
E100 VXX
01
281624
6430 Nordborg, Denmark
0030471
III
Dip switches for addressing and bus protocol selection are located under the lid of the actuator.
DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment
6
7
8
9
10
method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU.
For termination of last unit on the field bus, turn DIP Switch 8 ON.
ON
Dip switch 9 is not used.
OFF
Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON).
When the protocol is changed on DIP Switch 10, a power cycle is required.
Select Valve Type
MSV:3 / 32802
(default AB-QM DN125)
Select Valve Type
MSV:3 / 32802
(default AB-QM DN200)
Serial number and QR code can be removed from the
NovoCon® L/XL label and added to installation drawing.
MADE IN SLOVENIA
E100 VXX
E100 VXX
01
281624
281624
0030471
0030471
Select application
MSV:10 / 32811
Heating (default)
Cooling
Select application
MSV:10 / 32811
Heating (default)
Cooling
01
Device Object
Instance Number
Design Flow Rate
Activate calibration
AV:30 / 32796 Heating
MSV:0 / 33284 state 2
AV:31 / 32798 Cooling
or use manual calibration
Design Flow Rate
Activate calibration
AV:30 / 32796 Heating
MSV:0 / 33284 state 2
AV:31 / 32798 Cooling
or use manual calibration
AQ321852892717en-010301