Danfoss FCM 300 Series Impostazione rapida - Pagina 4
Sfoglia online o scarica il pdf Impostazione rapida per Convertitore multimediale Danfoss FCM 300 Series. Danfoss FCM 300 Series 5.
Anche per Danfoss FCM 300 Series: Impostazione rapida (2 pagine), Impostazione rapida (2 pagine)
3 Start the FC motor
Connect mains. LED 302 (green) lights up to indicate
that the power is on. In Profibus versions, LED 303 will
flash. For further information on Profibus, please see the
Profibus manual.
Connect terminal 4 and 6 to the start button (see fig. 1).
Connect terminal 2, 7 and 8 to the potentiometer (see
fig. 1).
Use the start button to start the FC motor and adjust the
speed by means of the potentiometer.
Warning
The voltage on the FC motor is dangerous
when the motor is connected to mains.
Incorrect installation of the FC motor may
lead to material damage or serious injury
or it may be fatal.
4 Mount the inverter box cover.
Fastening torque: 2.2 - 2.4 Nm
Safety
Safety
Safety
Safety
Safety
All operations must be carried out by
appropriately trained personnel.
Use all lifting facilities provided e.g. both
lifting points, if fitted, or single lifting point, if
fitted*.
Vertical lifting - Prevent uncontrolled rotation.
Lift machine - Do not lift other equipment with motor
lifting points only.
Before installation check for fan cover damage, shaft
damage, foot/mounting damage, and loose
fasteners. Check nameplate details.
Ensure level mounting surface, balanced mounting,
not misaligned.
Gaskets, and/or sealants, and guards must be
correctly fitted.
Correct belt tension.
Please observe derating rules, see Design Guide
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
VLT
®
DriveMotor FCM 300 Quick Setup
* Note: maximum hand lift is 20 kg below shoulder, but
above ground level.
Max. weights:
-
Frame size 80: 15 kg
-
Frame size 90 & 100: 30 kg
-
Frame size 112: 65 kg
The voltage on the FC motor is dangerous
when the motor is connected to mains.
Incorrect installation of the FC motor may
lead to material damage or serious injury or
it may be fatal.
Consequently, the instructions in this Quick Setup as
well as national and local rules and safety regulations
must be complied with.
Touching the electrical parts may be fatal, even after the
mains supply has been disconnected.
Wait at least 4 minutes.
-
Installation must be fused and isolated correctly.
-
Covers and cable entries must be fitted
NB!:
It is the user's or certified electrician's
responsibility to ensure correct earthing and
protection in accordance with applicable national
and local requirements and standards.
Safety regulations
1.
The FC motor must be disconnected from mains if
repair work is to be carried out. Check that the mains
supply has been disconnected and that the
necessary time has passed (4 minutes).
2.
Correct protective earthing of the equipment must
be established, the user must be protected against
supply voltage, and the motor must be protected
against overload in accordance with applicable
national and local regulations.
In UL/cUL applications ETR provides class 20,
overload protection in accordance with the NEC
RCD's (ELCB relays), multiple protective earthing or
earthing can be used as extra protection, provided
that local safety regulations are complied with.
In case of an earth fault, a DC content may develop
in the fault current.
If RCD's are used, local regulations must be
observed. Relays must be suitable for protection of
3-phase equipment with a bridge rectifier and for a
brief discharge on power-up.
®
.