Danfoss VLT AutomationDrive FC 301 enclosure size A1 Manuale operativo - Pagina 13
Sfoglia online o scarica il pdf Manuale operativo per Convertitore multimediale Danfoss VLT AutomationDrive FC 301 enclosure size A1. Danfoss VLT AutomationDrive FC 301 enclosure size A1 16. Safe torque of, frequency converters
STO Technical Data
5 STO Technical Data
NOTICE
For technical specifications and operating conditions for the frequency converter, refer to the relevant operating
instructions/guides of the frequency converter.
NOTICE
The STO signal must be SELV or PELV supplied.
European directives
Safety standards
Safety function
Safety performance
Reaction time
Table 5.1 Technical Data
®
®
1) VLT
HVAC Drive FC 102, VLT
Refrigeration DriveFC 103, VLT
Drives with enclosure size F:
•
400 V: 450/500 kW (600/650 hp) – 800/1000 kW (1075/1350 hp) (High Overload/Normal Overload).
•
690 V: 630/710 kW (850/950 hp) – 1800/2000 kW (2400/2700 hp) (High Overload/Normal Overload).
®
2) VLT
Parallel Drive Modules:
•
400 V: 250/315 kW (350/450 hp) - 800/1000 kW (1200/1350 hp) (High Overload/Normal Overload).
•
690 V: 315/400 kW (350/400 hp) – 1000/1200 kW (1150/1350 hp) (High Overload/Normal Overload).
MG37D502
Operating Guide
EN ISO 13849-1
Machinery Directive
EN IEC 62061
(2006/42/EC)
EN IEC 61800-5-2
EN 50011
EMC Directive
EN 61000-6-3
(2014/30/EU)
EN 61800-3
Low Voltage Directive
EN 50178
(2014/35/EU)
EN 61800-5-1
Safety of Machinery
EN ISO 13849-1, IEC 62061, IEC 60204-1
Functional Safety
IEC 61508-1 to -7, IEC 61800-5-2
IEC 61800-5-2
Safe Torque Off (STO)
ISO 13849-1
Category
Cat 3
Diagnostic Coverage
DC: 90% (Medium)
Mean Time to Dangerous
MTTFd: 14000 years (High)
Failure
Performance Level
PL d
IEC 61508/IEC 62061
Safety Integrity Level
SIL 2, SIL CL2
Probability of
PFH: 1E-10/h; 1E-8/h for specific variants
Dangerous Failure
(High Demand Mode)
per Hour
Probability of
PFD: 1E-10; 1E-4 for specific variants
Dangerous Failure
(Low Demand Mode)
on Demand
Hardware Fault Tolerance
HFT: 0 (1oo1)
Proof Test Interval T1
20 Years
Mission time TM
20 Years
Input to output response time Maximum 20 ms, 60 ms for specific variants
®
AQUA Drive FC 202, and VLT
Danfoss A/S © 01/2018 All rights reserved.
IEC 60204-1
Stop Category 0
1), 2)
1), 2)
1), 2)
®
AutomationDrive FC 301/FC 302 High Power
5
5
11