OWNER'S MANUAL INSTALLATION INSTRUCTIONS
F. CONTINUOUS FAN
Select the desired Continuous fan speed when thermostat is set on
continuous fan operation by using the Yellow jumper wire.
NOTE: If installed with a two-stage outdoor unit, do not select HI
speed continuous fan. If HI is selected, low stage compression (low-
speed cooling) will also run HI fan speed possibly resulting in
insufficient dehumidification.
1. LO speed - factory setting, approximately 50% cooling mode
airflow.
2. MED speed - move connector to MED, approximately 65%
cooling mode airflow.
3. HI speed - move connector to HI, approximately 100% cooling
mode airflow.
G. LOW-VOLTAGE CIRCUIT
(FUSING AND REFERENCE)
The low-voltage circuit is fused by a board-mounted 5-amp
automotive fuse placed in series with the transformer SEC2 and the
R circuit. The C circuit of the transformer is referenced to chassis
ground through a printed circuit run at SEC1 connected to metal
standoff marked with ground symbol.
H. QUICK SET UP
(BASIC AIR HANDLER CONFIGURATION)
The following basic configuration of the air handler will provide best
performance of an Air Conditioner:
1. AUX HEAT KW/CFM - Select the heater range for the size
electric heater installed.
2. OUTDOOR UNIT SIZE - Select system size installed.
3. SYSTEM TYPE - Select system type AC.
4. AC/HP CFM ADJUST - Select NOM.
5. ON/OFF DELAY - Select 0/90 profile.
6. CONTINUOUS FAN - Select desired air handler when thermostat
is set to continuous fan.
The following basic configuration of the air handler will provide ARI
rated performance of a Heat Pump:
1. AUX HEAT KW/CFM - Select the heater range for the size
electric heater installed.
2. OUTDOOR UNIT SIZE - Select system size installed.
3. SYSTEM TYPE - Select system type HP-EFF.
4. AC/HP CFM ADJUST - Select NOM.
5. ON/OFF DELAY - Select 0/90 profile.
6. CONTINUOUS FAN - Select desired fan speed when thermostat
is set to continuous fan.
ACCESSORIES
AUXILLIARY TERMINALS
The Fan Control Board contains the following auxiliary terminals,
refer to Figure 6.
HUM1 and AUX1 are in common with SEC1, and thermostat
common.
HUM2 and AUX2 terminals are tied directly to the G terminal from
thermostat, and provide a 24 VAC hot signal whenever the G terminal
is energized.
HUMIDIFIER OPERATION WITH HUMIDISTAT
A standard humidistat can be used to operate a humidifier. The
HUM1 is internally connected to 24V Common (C), and HUM2 is
internally connected to (G). Refer to Figure 12 for typical Humidifier
wiring layout using HUM1 (C), and HUM2 (G).
Alternately, the 24VAC signal may also be sourced from the W1 and
Com (thermostat pigtail) connections when electric heaters are used
as a primary heating source (refer to Figure 13).
NOTE: When using a thermostat with built-in humidity control, the
above auxiliary terminals can be ignored, and the humidifier may be
sourced directly from humidity terminals located on the thermostat
itself.
DEHUMIDIFY CAPABILITY
The J1 jumper should always be removed from the Fan Control
Board for proper airflow operation.
Latent capacities for systems using the AHV are better than average
systems. If increased latent capacity is an application requirement,
the field wiring (thermostat pigtail) connections provides a (Dh) for
use with a standard humidity sensor/control (Refer to Figure 14 for
additional latent control). The AHV will detect a closed contact
between R and Dh (closing on a humidity rise) and reduce its airflow
to approximately 80% of nominal cooling mode airflow. This reduction
will increase the system latent capacity until the humidity falls to a
level which causes the humidity sensor/control to open its contacts.
When the contacts open, the airflow will return to 100% of the
selected cooling airflow. Refer to Figure 15 for Normal Airflow
Operation.
Figure 12
Figure 13
Humidifier Wiring for Electric Heat Primary
Figure 14
Figure 15
HEATER STAGING
The AHV modular fan control board is factory set for single-stage
electric heat operation. Refer to Table 3 for available heaters.
When two-stage electric heat is desired, the J2 jumper must be
removed. Refer to Table 3-2 for two-stage compatible heaters.
Removing J2 will allow second stage control by the indoor wall
thermostat (if multi-stage capable).
9
DUOTEC AIR HANDLER: AHV
Humidify
Humidifier Wiring
Heating Source
De-Humidify
Additional Latent Control
Normal Airflow Operation