Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. POSITIONING: These high bay controls should be installed to achieve correct
coverage of the area, see diagram A for the appropriate detection pattern. Avoid
locating this product where it is exposed to drafty conditions (exposed lobbies,
open ceiling voids or near fans) or near heat sources.
3. Make sure the power is isolated from the circuit.
The PIR should be connected as shown in diagram D:
SL
Switched Line out
L
Live in
N
Neutral in
DA -
DSI control line (Polarity independant)
DA +
DSI control line (Polarity independant)
SW1
Switch input
4. Knockout or drill the appropriate holes on the mounting plate for attaching the plate
to the ceiling or back box (if applicable). Feed cables through the appropriate (side
or rear) entry hole (see diagram E). Screw the back mounting plate to the ceiling
or back box via the mounting holes. Wire the cables into the sensor head block
terminal. Push the sensor head onto the mounting plate and align the side clips
with the slots on the sensor heads.
Start-up mode
When the PIR is powered up, it will switch on the load for 1 minute, the load will
then switch off and the PIR will enter its Operating Mode.
Time / Run-on / lux set up
The LUX adjuster spindle on the side of the PIR is used to regulate the automatic
daylight linked dimming function lux level (see diagram C opposite). This should be
adjusted in situ by rotating the LUX adjuster slowly anticlockwise (+ to -) so that the
desired level of brightness is achieved under the luminarie(s) being controlled.
Once the correct level is achieved and there has been no further adjustment to the
LUX spindle, the control will go through a 30 second delay before the automatic
closed loop control will start.
These controls incorporate a fixed 20 second fade rate from maximum to the set
back level.
Sensitivity
These controls incorporate a sensitivity adjuster, labelled 'SENS', to reduce the
range of detection from 100% to 50% in 9 steps (see diagram B opposite).
A: Detection diagrams
NARROW
SPOT
DETECTION (ND)
DETECTION (SP)
Mounting height
Mounting height
up to 12m
up to 20m
Perspective view -
Perspective view -
ceiling mounted
ceiling mounted
Up
to
15m
Up to 5m
Up to 3m
diameter
B: Adjusting SENSITIVITY & TIME
C: Adjusting LUX & RUN-ON
Typical settings
max
min
max
min
SENS
TIME
50%
100%
40m
10s
20m
20s
10m
40s
5m
80s
2.5m
D: Wiring diagram, HBA PIR (xx) DSIP controlling several DSIP dimmable ballasts
L
230 VAC
N
Mains
rated
retractive
Optional
wall switch
L
other load
or rocker
SW
wall switch
1
(toggled)
E: Mounting plate fixing
Knock out mounting
holes or pre-drill
pilot holes.
For side entry -
For cable entry
knock out side
from above -
mounting hole
knock out central
from mounting
mounting hole
plate and device
WIDE
DETECTION (WD)
Mounting height
up to 14m
Perspective view -
ceiling mounted
Up to 28m
diameter
Typical settings
max
min
max
min
LUX
RUN ON
INFINITE
0s
30m
1m
20m
2m
15m
5m
10m
DSI
DSI
Ballast
Ballast
DSI Control Lines
DANLERS DSIP
High Bay control
(Absence)
N
SL
Join device to
mounting plate via
mounting clips
Connect wires to
terminal block on
the device