Dantherm Classic 20 CS020020B5 Manuale informativo sul prodotto - Pagina 11

Sfoglia online o scarica il pdf Manuale informativo sul prodotto per Condizionatore d'aria Dantherm Classic 20 CS020020B5. Dantherm Classic 20 CS020020B5 16.

Dantherm Classic 20 CS020020B5 Manuale informativo sul prodotto
Classic 20 ACU Installation, Operating & Maintenance Manual

MAINTENANCE

6
6.1

Preventative Maintenance Schedule

Dantherm Air Handling Inc Air Conditioner Preventative Maintenance Schedule
Maintenance Item
1 Check enclosure air or ambient air filter (If applicable)
2 Condenser coil cleaning
3 Rotating component current check
4 Functional Check
5 Fan/Blower Inspection
6 Evaporator coil cleaning
7 Cabinet cleaning & Corrosion Check
8 Condensate drains
9 Refrigerant charge
10 Lubrication
* Can be extended to 6 months after initial visits if no cleaning is required.
Notes:
1
The internal/external filter (if applicable) shall be checked on a regular basis dependent on environmental conditions and replaced as necessary.
2
Periodically the coils should be cleaned. Once the coils become visibly coated with dust it is recommended that they be cleaned with a brush or
compressed air. Both sides of the coils should be inspected. The condenser coil may be washed with a commercial coil cleaning solution.
3
Check run amps on rotating components and record to enable assessment of potential failure.
4
Perform Self Test Function in acordance with Operation Manual. Complete general check of component mounting.
5
Condenser and evaporator blowers require no maintenance other then periodic inspection. In the event of dust build-up clean the blowers.
6
The cabinet can be cleaned with a sponge and warm, soapy water or a mild detergent. Do not use bleach, abrasive chemicals or harmful solvents.
Check for signs of corrosion and treat as necessary.
7
Check the drain and drain tube for obstructions. If a commercial drain solvent is used, flush out the drain pan and system with fresh water to prevent
corrosion.
8
Under no circumstance must the access port covers be removed, adjusted, or tampered with other than by a certified technician.
9
Rotating component bearings must be lubricated using SAE20 weight non detergent oil.
10
All maintenance inspections must be recorded with time, date & details of activity.
AC-2 CS020020 USACG-6 Manual Rev B
3 or 6
6 Monthly
Yearly
5 Yearly
Monthly
X*
X*
X
X
X
X
X
X
X
Page 11 of 16
X