Contax 24 OPzV 3000 Installazione
Sfoglia online o scarica il pdf Installazione per Camera Accessories Contax 24 OPzV 3000. Contax 24 OPzV 3000 3.
VHB Industrial Batteries Ltd.
VARTA OPzV range
4 OPzV 200...24 OPzV 3000
Application
VARTA OPzV Valve Regulated OPzV batteries are especially
suitable for applications with discharge over a long period
where maintenance-free operation is required.
The electrolyte is fixed as a gel.
Typical applications include reserve power supplies for
telecommunication equipment and industrial plants and
also safety power supply equipment for lighting,
automation and metering systems.
Construction
Positive Electrode
Negative Electrode
Separation
Casing Material
Electrolyte
Terminal Design
Connectors
Vent Plugs
Charging
Temperature Range
VHB Industrial Batteries Ltd.• 72 Devon Road, Unit 22, Brampton, Ontario L6T 5B4
Tel: (905) 790-0730 • 1-888-VHB-BATT • Fax: (905) 790-0744 • E-mail: [email protected]
Tubular plate with VARTA-
Calcium-Tin alloy
Grid plate with calcium alloy
Micro-porous separator,
Combined with corrugated
Separator
Styrene acrylonitrile (SAN),
impact resistant
Dilute sulphuric acid
Fixed as a gel
Leakproof safety pole with
brass insert, M10
Solid copper
(30 x 3 mm), insulated,
bolt-on type,
for horizontal installation
optional flexible cable
2
connector (70 mm
) 3/0
Safety pressure relief valve
Float charge voltage:
o
2.23 volts/cell at 20
C
o
o
-10
...+45
C
o
(Preferred value 20
C)
Installation
VARTA OPzV batteries are mounted as standard in the
upright position on insulated racking. For space saving
installation it is also possible to install them in horizontal
position (plates must be in the vertical plane, max. 1500 Ah)
The safety provisions of the national and international
standards must be observed.
Features
2V single cells
Maintenance-free operation throughout its operational
life due to valve regulated construction
High level of operational safety due to pressure
relief safety valve, safety pole, insulated connectors
and fixed electrolyte
Economic operation in capacitive discharge over
several hours
Space saving installation due to optimized set-up
Low ventilation requirement, using the reduction
factors
04.09.01 0298 na