Local Code Approval
While it is not detailed in codes, the following rules should be followed for selecting Belimo
actuators for replacement:
Check the technical specifications to ensure an "equal or better" actuator is used.
• Temperature – the replacement actuator shall have been UL555S tested at the same or
better temperature as the original actuator. 250˚F or 350˚F are standard.
• Time – the replacement actuator shall drive open and spring closed at a speed equal or
faster than presently required by codes. (The AHJ may grant an exception and
"grandfather" slower actuators where the original actuator was slower.)
• Torque – replacement actuator shall have equal or greater torque than the failed
actuator.
• Voltage – replacement actuator shall have the same voltage rating as the original.
• Amperage – the replacement actuator(s) shall not draw more amperage than the
original(s) and cause the total connected amp draw on a circuit breaker to be greater
than allowed by electrical code.
• Final Testing – actuated damper and associated devices shall be tested for proper
operation. See Fire Marshal Notification Form on last page.
In all cases, installation must comply with any and all local electrical and life
safety codes. Operation of the system after installation must be performed to
verify proper damper cycling. Final checkout requires verifying correct function.
NEGATOR SPRING DAMPERS
Where old negator spring damper motors were replaced by a Honeywell, the spring
should have been removed and a new thermal sensor installed. If this has not been
done, call Belimo for special instructions.
Some instructions are available at:
https://www.belimo.us/solutions/actuators/product-documentation/damper-actuators-fire-and-
smoke#tab2
Disconnect and lock out power before starting to disconnect old motor.
Air Balance Honeywell ML&MS Types to Belimo FSxx
(Mnemonic device: TTT-VAT)
WARNING!
WARNING!