Belimo VRD3-RE2-SET Manuale di installazione - Pagina 8
Sfoglia online o scarica il pdf Manuale di installazione per Motore Belimo VRD3-RE2-SET. Belimo VRD3-RE2-SET 9.
VAV-Universal Retrofit-Set
Setting and first commissioning (continued)
min
[Potentiometer or Tool (PP command)]
Note concerning difference
min
VRD2
The adjustment range of the operating mode
with:
– VRD2 refers to 0 ... 100% of
max
– VRD3 refers to 0 ... 100% of
nom
The
setting of the VRD3 thus behaves in
min
compatible fashion with the new VAV generation
(starting with 200), i.e. VAV-Compact L/N/SMV-
D2-MP, VRP-M.
VRD3-RE2 setting with VAV adjustment tool ZTH-VAV
Operating menu VRD3-RE2
8 / 9
Installation
Die operating volumetric flow settings
/
setting
max
VRD3-RE2:
a) directly on the adjustment potentiometer (analogous to the VRD2)
0 ... 100% of
min
30 ... 100% of
max
b) with VAV adjustment tool ZTH-VAV (PP command)
To write a value – with PP command - into the VRD3-RE2 both of the potentiometers
must be at the Tool position. If the potentiometer(s) is/are set to «Tool» with ZTH-VAV
max
connected , then the menu may under certain circumstances need to be refreshed through
actuation of the ↑↓ keys. For function, see following illustration:
Adjustment potentiometer
20
10
0
VRD3
setting VRD3,
min
Automatic adjustment via
potentiometer position
Potentiometer:
– Tool: ZTH value
– 0 ... 100%: Potentiometer value active
The
value must always be set higher than the
max
controller will operate with the
The entire BELIMO product range with PP connection can be set and controlled with the VAV
adjustment tool ZTH-VAV. The connection to the VRD3-RE2 is provided by the RJ «Service»
socket or at the PP connection (terminal 4), e.g. in the control cabinet.
Option
Volumetric flow – actual
value
Volumetric flow - setpoint
Current pressure value
Specify CAV steps
Mode
min
max
nom
∆p @
* Function is displayed, starting with ZTH-VAV Firmware V1.02 or higher (starting 0.2008).
See also Release Note ZTH-VAV, www.belimo.eu
M4-VAV-Universal Retrofit Set • en • v1.1 • 04.2011 • Subject to changes
min
nom
nom
/
min
max
40 50
60
30
70
80
90
100
parameterised
value
45 %
0 ... 100%
Tool
volume as setpoint in CAV mode.
min
Unit
%
%
Pa
–
–
setting
%
setting
%
VAV box
%
Pa
nom
and
can be adjusted two different ways on the
max
Tool
ZTH-VAV
▲ ▼ – + OK
ZTH-VAV
r = read
w
r
w = write
(PP)
effective value
45 %
value; otherwise the VRD3-RE2
min
Range/setting
0 ... 100% [of
]
nom
0 ... 100% [
...
]
min
max
0 ... 300 Pa
Auto – CLOSED – OPEN –
–
– Stop
max
0 ... 10V, 2 ... 10V
0 ... 100% [of
]
nom
30 ... 100% [of
]
nom
Nominal setting = 100%
differential pressure pending with
nom
and
min
Function
Commissioning,
Service function
min
Settings,
modifications
OEM setting
www.belimo.eu