Aplisens PC-29A Manuale d'uso - Pagina 19

Sfoglia online o scarica il pdf Manuale d'uso per Accessories Aplisens PC-29A. Aplisens PC-29A 20. Pressure transmitters

Aplisens PC-29A Manuale d'uso
11.

INSPECTIONS. SPARE PARTS

11.1.

Periodic inspections

During inspection, the connectors should be checked for loose connections and leaks, the
electrical connectors should be checked with regard to tightness and the state of the
housing, gaskets, cable glands, and the diaphragm seals should be checked for tarnishing
and corrosion. Readability of the tag should also be checked.
11.2.

Unscheduled inspections

If the transmitter is installed in a location where it could be subjected to mechanical
damage, electrical surges or malfunction is found - inspect it as needed.
In case of lack of signal in the transmission line or its incorrect value, check the state of the
cable, of the connection on terminals, etc. Determine whether the values of the supply
voltage and load resistance are correct. If the communicator is connected to the
transmitter power supply line, an indication of a fault line may be the message "No
response" or "Check connection". If the line is in order, check operation of the transmitter.
12.

SCRAPPING, DISPOSAL

Waste or damaged transmitters should be dismantled and disposed of in
accordance with Directive (2012/19/EU) on waste electrical and electronic
equipment (WEEE) or returned to the manufacturer.
12.1.

Additional information

The manufacturer reserves the right to make constructional and technological changes
which do not lower the quality of the transmitters.
04.A.004
IO.PCE-28....PC-29.Exd