Aplisens ZSP-41/2 Manuale d'uso - Pagina 11

Sfoglia online o scarica il pdf Manuale d'uso per Convertitore multimediale Aplisens ZSP-41/2. Aplisens ZSP-41/2 16.

9.

TECHNICAL PARAMETERS

9.1.

Electrical parameters of ZSP-41 and ZSP-41/2

Two-wire power supply
Power consumption
When switching on in the ZSP-41 isolator, the maximum temporary power
consumption is about 3,5VA (power necessary to start up the internal
converter)
Input signal
Input resistance
Output signal
Output resistance
Insulation type
Resistance to electrical breakdown
Conversion errors
- basic error (***)
- temperature change effect
- load resistance change effect
- power voltage change effect
(***) ERROR VALUE REFERS TO RANGE SETTING 4...20mA/4...20mA WITHOUT
POWER SUPPLY TO INPUT CONVERTER. WITH OTHER SETTINGS (WITHOUT
ADDITIONAL CALIBRATION) BASIC ERROR IS 0.25% - not applicable to
03.B.005
IO.ZSP-41.SP-11.SP-02
24V DC ±20%
<2 VA with ZSP-41
<3 VA with ZSP-41/2
0...20mA, 4...20mA,
two-wire (4...20mA + converter power
supply)
0...10V
≥ 50kΩ (voltage input)
≤ 50Ω (current input)
0...20mA, 4...20mA,
0...10V
0...500 Ω (current output)
≥ 1 kΩ (voltage output)
optoelectronic
1.5kV AC 50Hz 1min
≤±0.16%
≤±0.1%/10°C
≤±0.1%/100Ω (current output)
≤±0.1% with ≥1kΩ (voltage output)
≤±0.1%
OWC
version.