Conventional Marine Indoor
Manual Call Point Installation Guide
General
The Conventional Marine Indoor Manual Call Point-Red, part number 55100-021 MAR,
model number MCP2A-R470SF-A071-02 is supplied with a backbox for surface mounting.
The call point is 'Type A' and is suitable for indoor use only. For fl ush mounting, a standard
electrical outlet box with a minimum depth of 25mm is required.
Installation – General
The installation must conform to BS5839: Part 1 (or applicable local codes).
Installation
1.
Fit the backbox (Fig 1) to the wall.
2.
Run the cables into the backbox and connect them to the terminal block as shown in
Fig 2. Ensure that functional earth/screen continuity is maintained.
3.
Unlock the small front cover by inserting the forked key and pushing it home. Remove
key, slide the cover down and remove the deformable element. Connect the terminal
block as shown in Fig. 2, secure the call point to the backbox and refi t the deformable
element as required. Finally, replace the front cover in the reverse order in which it was
removed and push it up until it locks.