5.2 LAMP TEST
5.3 RELAY TEST
PUSHBUTTON
The required relay to be tested is
selected with MODE button. Trip (),
Fault(), Alarm() or Fan() can
be selected.
When the relay name is on display, hold
MODE button pressed during 5
seconds. The test screen of this relat
will open. The initial value of "0" is
displayed.
Arrow up button activates the relay
output and displays "1" on the screen.
Arrow down button deactivates the relay
output and displays "0" on the screen.
Mode button will switch to next relay or
parameter display.
When exiting the PROGRAM mode, the unit makes a LAMP
TEST during 5 seconds.
During LAMP TEST all leds will turn on. At the end of 5
seconds or if MODE button is depressed the LAMP TEST is
terminated.
If no pushbutton is depressed during 3 minutes, the
PROGRAM mode will be automatically terminated.
In this case LAMP TEST is not performed.
OPERATION
Exiting the relay test display will cause the relay resume
normal operation.
-12-
V-3.0
(14.09.2016)