Datakom DPR-145 Manuale d'uso - Pagina 8

Sfoglia online o scarica il pdf Manuale d'uso per Relè Datakom DPR-145. Datakom DPR-145 19. Temperature protection relay

DPR-145 User Manual

3. DISPLAYS

Mod Leds
Test Led
SELECTED CHANNEL LEDS: indicates
the related channel to alarm or
information on display.
MOD LEDS: indicated the current mode
of operation.

3.1 MODES OF OPERATION

The unit has 4 operating modes: SCAN, AUTO, MAN, MAX.
Every depression of the MODE button switches the unit to the next operating mode.
Related mode led will turn on. Channel leds on the right side (1,2,3,4) indicate the
related channel number.
• SCAN: Displays channel temperatures, switches to the next channel every 5
seconds.
• AUTO: Displays the temperature of the highest channel.
• MAN: Displays the temperature of the selected channel. Channels may be
scrolled with
• MAX: Displays the maximum recorded temperature of the selected channel.
Channels may be scrolled with
NOTE: If any of
the unit will automatically switch to the MANUAL mode. If no pushbutton is depressed
during 30 minutes, it will resume previous mode.
and
pushbuttons.
or
pushbuttons is depressed in SCAN or AUTO modes, then
ALARM LEDS: indicates the type of
alarm if any.
TEST LED: turns on during lamp test or
relay test.
PPROGRAM LED: turns on in program
mode.
and
pushbuttons.
-8-
V-3.0
(14.09.2016)
Alarm Leds
Selected
Channel Leds
Program Led