Elsist Pure 2000 Manuale di istruzioni - Pagina 14
Sfoglia online o scarica il pdf Manuale di istruzioni per UPS Elsist Pure 2000. Elsist Pure 2000 18. Single phase line interactive sinewave ups
PURE 1000●2000●3000
LINE INTERACTIVE SINGLE-PHASE
SINEWAVE
3.7 Falult reference code
Fault events
Bus fail
Inverter high
Inverter low
Output short
Overload
Battery over
Temperature high
4.
Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below:
SYMPTOM
No indication and alarm even
though the mains is normal.
EPO displayed on LCD and
alarm is sounding.
Load icon flashes on LCD display
and alarm is sounding every
second.
Overload codes displayed on
LCD display and alarm is
sounding every second.
Fault code is shown as 14 and
alarm is continuously sounding.
Fault code is shown as 01, 03, 08,
09 on LCD display and alarm is
continuously sounding.
Battery backup time is shorter
than nominal value
5.
Storage and maintenance
The UPS system contains no user-serviceable parts. If the battery service life (2/3 years) has been exceeded,
the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility.
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During
storage, recharge the battery in accordance with the following table:
Storage Temperature
-25°C - 40°C
40°C - 45°C
Ver.00 09 March 2018
Fault occurring mode
Line mode
00
02
06
14
08
POSSIBLE CAUSE
The AC input power is not
connected well.
The AC input is connected to the
UPS output.
EPO function is activated.
The external or internal battery is
incorrectly connected.
UPS is overload
The UPS shut down automatically
because short circuit occurs on the
UPS output.
A UPS internal fault has occurred.
Batteries are not fully charged
Batteries defect
Recharge Frequency
Every 3 months
Every 2 months
Fault occurring mode
Battery mode
08
01
03
11
07
15
09
REMEDY
Check if input power cord firmly
connected to the mains.
Plug AC input power cord to AC
input correctly.
Set the circuit in close position to
disable EPO function.
Check if all batteries are
connected well.
Remove excess loads from UPS
output.
Check output wiring and if
connected devices are in short
circuit status.
Contact your dealer
Charge the batteries for at least 5
hours and then check capacity. If
the problem still persists, consult
your dealer.
Replace the battery.
Charging Duration
1-2 hours
1-2 hours
14