Dusol DS60W Manuale d'uso - Pagina 9

Sfoglia online o scarica il pdf Manuale d'uso per Pannello solare Dusol DS60W. Dusol DS60W 11.

DUSOL Solar Photovoltaic module
MADE IN DUBAI

5. Wiring and connection

a) Make wiring by Multi-connecting cables between the PV modules in series or parallel
connection, which is determined by user's configuration requirement for system power, current
and voltage.
b) PV module connected in series should have similar current. Modules must not be connected
together to create a voltage higher than the permitted system voltage(1000VDC), as reference the
maximum number of modules in series (N) can be easily calculated by dividing the Maximum
System Voltage of the modules by the respective Voc value of the module. Any more please
always take into consideration the variation of the voltage under different temperatures, the Voc
of the modules will be rise when the temperature drops.
For example: with DS72300M-72 modules (Max. System voltage is 1000V) the maximum series
modules configuration number should NEVER can exceed N= 22 (1000V/45.2V = 22.1)
c) PV module connect in parallel should have similar voltage. As reference the maximum number
of modules in parallel can be easily calculated by dividing the maximum rated current (indicated
in the electrical specification) by Isc value of the module, and then plus 1. Any more please
always take into consideration the variation of the current under different temperatures, the Isc of
the modules will be rise when the temperature goes up.
d) Open the connection box of the control system and connect the cabled from the PV arrays to
the connection box in accordance with the installation indication of the PV control systems. The
cross-sectional area and cable connector capacity must satisfy the maximum short-circuit of PV
system (For a single component, we recommended the cross-sectional area of cables is 4mm2
and the rated current of connectors is more than 10A), otherwise cables and connectors will
become overheating for large current. Please pay attention: the temperature limit of cables is
85℃ and the temperature limit of connector 105℃)
e) All module frames and mounting racks must be properly grounded in accordance with local
and national electrical codes. Attach the equipment grounding conductor to the module frame
using the hole and hardware provided. Note that a stainless steel star washer is used between the
ground wire and the module frame. This washer is used to avoid corrosion due to dissimilar
metals. Tighten the screw securely.
f) These modules contain factory installed bypass diode .if these modules are incorrectly
connected to each other, the bypass diodes, cable or junction box may be damaged.
9