Dust Care 4000 Quiet Series Manuale di installazione - Pagina 5
Sfoglia online o scarica il pdf Manuale di installazione per Aspirapolvere Dust Care 4000 Quiet Series. Dust Care 4000 Quiet Series 11. Central vacuum systems
EXISTING CONSTRUCTION
From the attic down
In order to find where to drill the holes for the branch lines into the plates, establish a
reference point for the Inlet valve by measuring from the center of the intended inlet
valve location to the nearest corner of the room in which the inlet is to be located.
Find this corner from the attic by peeling back the insulation to expose the top plate.
Measure the same distance you measured below from where the top plates form that
corner (illustration 1). You should now be in a straight vertical line directly above the
Inlet valve location. Remember whether you measured your reference point from
the inside or outside corner.
Drill a 2 1/2" hole into the center of the top plate. After you have completed this,
you can visually re-check, with the use of a flashlight, that the space between the
studs is free of obstruction.
As our illustration shows, you will be working in a confined space with very little head
room. Use any number of extension drill bits to enable you to get to the intended
location of the inlet valves (illustration 2).
Measure and cut pipe from the plate to Inlet valve hole below and feed pipe through
hole into space between wallboard.
It is important that you have all the necessary tools with you in the attic to save you
avoidable trips through the small access openings, through which attics are commonly
accessible (illustration 2).
If, due to lack of adequate vertical space, the entire length of pipe can't be inserted
in one piece, then shorter sections can be cut and glued together with the use of
couplings and fed into the hole in the top plate section by section until it reaches
the inlet valve opening.
Note:
IT IS EXTREMELY IMPORTANT TO VERIFY THAT THE WALL DOES NOT
CONTAIN ANY ELECTRICAL CONDUCTORS WHICH MAY INTERFERE WITH
THE DRILL BIT.
Illustration 1
8
Follow steps 5 through 9
of the mounting plate
installation diagram for
the installation of mount-
ing plates and Inlet valves.
YOU ARE NOW READY
FOR THE INSTALLATION
OF THE MAIN LINE.
Illustration 2
The main line connects the entire system from the inlet valves to the power
unit. It carries the low-voltage wire along its entire run. During the layout process
you checked carefully for possible obstructions along the intended run, such as
double joists, ducts, electrical wiring or water lines. By-pass these obstructions
as per our illustrations.
Glue main line fittings to the exposed branch pipes above the plates. Make sure each
fitting points in the direction of the power unit. Measure and cut the pipe lengths for
the main line and glue into hubs of fittings leading from branch to branch. Apply glue
to both ends of the pipe and to the inside of the hub then twist pipe into hub until
firmly seated. Glue will set instantly.
Fasten low-voltage wire to pipe run with cable ties
approximately every 6' and at each Ell. This will pre-
vent drooping, possible damage to wire insulation or
ripping. Electrical tape may be used if double-wrapped
around wire and pipe. For the proper way of splicing,
refer to the section on wiring.
The finished installation in the illustration shows an air
vent obstructing an intended branch line (illustration
4, dotted line).
A 45° wye can be advantageously utilized to by-pass this and similar obstructions by
installing the wye into the main line further downstream.
The use of a 45° wye will save you the additional installation time of two extra fittings.
The 180° "loop" shown is further explained in illustration 11.
From basement up
Simply reverse the procedure of the branch line installation, as your main run will
be located below instead of above the inlet valves. When the main run is installed
between, or on the underside of the floor joists, the risers and drops can be concealed
in a variety of ways.
Illustration 5
Illustration 6
Illustration 4
Illustration 9
9