DV Power TRT30C Manuale - Pagina 16
Sfoglia online o scarica il pdf Manuale per Trasformatore DV Power TRT30C. DV Power TRT30C 19. Three-phase transformer, turns-ratio test instrument
TRT30C
5 Technical Data
5.1 Mains Power Supply
- Connection:
- Voltage:
- Frequency:
- Input power:
- Fuse:
5.2 Output data
- Test Voltage
5.3 Measurement
- Ratio Measuring Range
- Typical Ratio Accuracy:
0.8 - 999: ±0.05 %
0.8 - 999: ±0.05 %
0.8 - 999: ±0.05 %
- Guaranteed Ratio Accuracy:
0.8 - 999: ±0.125 %
0.8 - 999: ±0.125 %
0.8 - 999: ±0.125 %
- Excitation Current Range
- Typical Excitation Current Accuracy
- Guaranteed Excitation Current Accuracy ± (0.25% + 1 mA)
- Excitation Current Resolution
0 – 9.9999 mA
10 – 99.999 mA
100 – 999.99 mA
1 – 2 A
- Phase Angle Range
- Typical Phase Angle Accuracy
- Guaranteed Phase Angle Accuracy
- Phase Angle Resolution
5.4 Environmental conditions
- Operating temperature
- Storage temperature
- Maximum relative humidity
5.5 Dimensions and Weight
- Dimensions (W x H x D)
- Weight
M-T030CN-203-EN
According to IEC/EN60320-1; UL498, CSA 22.2
90 – 264 V AC
50 – 60 Hz
200 VA
2 A / 250 V, type F, but not user replaceable
8 V AC, 40 V AC, 80 V AC
3 x (8, 40, 80)3 V AC
0.8 to 15 000 (5-digit Resolution)
1000 - 3999: ±0.05 %
1000 - 3999: ±0.1 %
1000 - 3999: ±0.1 %
1000 - 3999: ±0.125 %
1000 - 3999: ±0.25 %
1000 - 3999: ±0.25 %
0 – 2 A
± (0.25% + 500 μA)
0.1 μA
1 μA
10 μA
100 μA
360 Degrees
± 0.05 Degrees
± 0.1 Degrees
0.01 Degree
-10 °C – +55 °C / +14 °F – +131 °F
-40 °C – +70 °C / -40 °F – +158 °F
95 % non-condensing
480 x 197 x 395 mm / 18.9 x 7.75 x 15.55 in
8 kg / 17.5 lbs
16
4000 - 15000: ±0.1 %
4000 - 15000: ±0.2 %
4000 - 15000: ±0.2 %
4000 - 15000: ±0.25 %
4000 - 15000: ±0.5 %
4000 - 15000: ±0.5 %
Technical Data
@80 V AC
@40 V AC
@8 V AC
@80 V AC
@40 V AC
@8 V AC