Sfoglia online o scarica il pdf Manuale per Unità di controllo Bender LINETRAXX MRCDB423. Bender LINETRAXX MRCDB423 20. Modular residual current device type b for additional protection (protection against indirect contact) in earthed systems (tn and tt systems)
Measuring current transformers
6.3
Fastening
CTBC20(P), CTBC35(P)
6.4
Mounting instructions
PE
L1
L2
L3
N
P1 (K): YE
All current-carrying cables must be routed together through
the measuring current transformer. Never route an existing
protective conductor through the measuring current trans-
former.
The cables must be centred in the measuring current trans-
former.
6.5
Shielded measuring current transformer variants
When used in outgoing circuits with high load or inrush currents, local saturations of the magnet-
ic core material of the measuring current transformers can occur. It is therefore recommended to
use the shielded P versions to prevent nuisance tripping.
The values are listed in the technical data and refer to a correctly selected internal diameter of the
measuring current transformer: d2 ≥ 2 x d1 (cable diameter).
16
MRCDB423_D00396_01_M_XXEN/06.2021
CTBC60(P)
P2 (L): GY
CTBC120(P) ... CTBC210(P)
The primary conductors may only be bent from the specified
minimum distance. The minimum bending radius specified by
the manufacturers must be observed.
* Distance to 90° angle = 2 x external diameter
To prevent nuisance tripping, the measuring current trans-
formers should not be completely filled with cables. The inter-
nal diameter of the current transformer should be at least
twice the diameter of the conductor bundle to be measured.
The following applies: d2 ≥ 2 x d1
Type
a
b
CTBC20(P) 31.4
49
CTBC35(P) 49.8
49
CTBC60(P)
56
66
CTBC120(P) 103
81
CTBC210(P) 180
98
*
*
c
2 x ø 5.5
2 x ø 5.5
3 x ø 6.5
4 x ø 6.5
4 x ø 6.5