Bender CD440 Manuale di avvio rapido
Sfoglia online o scarica il pdf Manuale di avvio rapido per Relè Bender CD440. Bender CD440 8. Multifunctional voltage relay
Quickstart
VMD461 with CD440
Multifunctional voltage relay
Intended use
The multifunctional voltage monitoring relay VMD461 monitors frequen-
cies, undervoltages and overvoltages in DC, AC and 3(N)AC systems. The
phase voltages and/or line-to-line voltages are measured as r.m.s. value
and are continuously shown on the device display. The measured value re-
quired to trigger the alarm relay is stored. The VMD461 features additional
measuring functions for:
ROCOF df/dt
Vector shift monitoring
Unbalance monitoring
Phase sequence monitoring
The corresponding ANSI codes for all available measuring functions are provided.
Configurable delay times allow considering special installation-specific properties (e.g. device-specific
start-up procedures). The VMD461 requires an external supply voltage.
The optional use of a CD440 coupling device extends the voltage range that can be monitored to DC/
3AC 1200 V or 1AC/3NAC 690 V. Any other use than that described in this manual is regarded as impro-
per. The quickstart does not replace the manual of the device. Download:
Safety instruction
Danger of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
DANGER
Before installing and connecting the device, make sure that the installation has
been de-energised. Observe the rules for working on electrical installations.
Dimension diagrams VMD461 (left) und CD440 (right) in mm
74
VMD461_D00314_00_Q_XXEN/10.2018
An electric shock
Damage to the electrical installation
Destruction of the device
108
98
EN
www.bender.de/manuals
71,7
93,0
1